CIRCULATING AIR SUPPLY

WARNING:

Do not allow combustion products to enter
the return air ductwork or the circulating air

supply. Failure to prevent the circulation of

combustion products into the living space can
create potentially hazardous conditions including

carbon monoxide poisoning that could result in

personal injury or death.

All return ductwork must be secured to the unit
with sheet metal screws. All return ductwork
must be adequately sealed and all joints must be
taped. When return air is provided through the

bottom of the unit, the joint between the unit and

the return air plenum must be air tight.

The roof curb or cement pad on which the unit is

mounted must provide sound physical support of

the unit with no gaps, cracks, or sagging between
the unit and the curb or pad.

Return air and circulating air ductwork must not
be connected to any other heat producing device
such as a fireplace insert, stove, etc. Doing so

may result in fire, explosion, carbon monoxide

poisoning, personal injury, or property damage.

Air Ducts

This unit is designed only for use with a supply and return
duct. Air ducts should be installed in accordance with the
standards of the National Fire Protection Association
“Standard for Installation of Air Conditioning Systems”
(NFPA 90A), “Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems” (NFPA
90B), and all applicable local codes. NFPA publications

are available by writing to: National Fire Protection

Association, Batterymarch Park, Quincy, ME 02269 or
visit www.NFPA.org on the web.

• Design the duct work according to Manual D by the Air

Conditioning Contractors of America (ACCA).

• The ducts must be properly sized not to exceed the unit

maximum ESP rating at 400 scfm per nominal ton of
cooling capacity.

• Duct work should be attached directly to the unit flanges

for horizontal applications.

• If roof curb is installed, the ducts must be attached to

the curb hangers, not the unit.

• It is recommended that the outlet duct be provided

with a removable access panel. The opening should
be accessible when the unit is installed in service and
shall be sized so that smoke or reflected light may be
observed inside the casing to indicate the presence of
leaks in the heat exchanger. The cover for the opening
shall be attached in a way that will prevent leaks.

• If outside air is utilized as return air to the unit for

ventilation or to improve indoor air quality, the system
must be designed so that the return air to the unit is not
less than 50° F (10° C) during heating operation.

• If a combination of indoor and outdoor air is used, the

ducts and damper system must be designed so that the
return air supply to the furnace is equal to the return air
supply under normal, indoor return air applications.

Air Filter Requirements

WARNING:

Never operate the unit without a filter in place.
Dust and lint could accumulate on internal parts,

resulting in loss of efficiency, equipment damage

and possible fire.

• This unit is not supplied with air filter(s) and has no

factory equipped means for accommodating internal
filter(s). A suitable air filter must be installed upstream
of the evaporator coil of the return air system. Refer to

Table 1

for recommended filter sizes.

• All return air must pass through the filters before entering

the evaporator coil.

It is important that all filters be kept

clean and replaced frequently to ensure proper operation
of unit. Dirty or clogged filters will reduce the efficiency
of the unit and result in unit shutdowns.

• Air filter pressure drop must not exceed 0.08 inches WC.

• Horizontal and downflow Installations require the air

filter system be installed in the return air ductwork.

NOTE TO INSTALLER: After installing or replacing the
filtration system for this unit, add the following statement

on or adjacent to the filter service panel:

“Replace

filter(s) installed in your system only with the same
dimensional size filters that are being replaced.”

Table 1. Air Filter Requirements

NOMINAL
COOLING

(TONS)

APPROXIMATE

AIR FLOW

RANGE (CFM)

APPROX.

FILTER AREA

(SQ. IN.)*

RECOMMENDED

FILTER SIZE

(IN. X IN.)

2

700 - 900

450

20 x 25

3

1,000 - 1,300

625

25 x 25

4

1,500 - 1,900

915

18 x 25 (2 required)

5

1,600 - 2,000

975

20 x 25 (2 required)

* Based on velocity of 300 ft/min for disposable filters.

• The unit installation shall avoid areas where condensate

drainage may cause problems by dropping on planters
or patios, etc. Also verify exhaust gases will not
impinge on windows or building surfaces, which may
be compromised or damaged by condensation.

• Do not install the unit such that exhaust from the vent

termination is directed into window wells, stairwells,
under decks, or in alcoves or similarly recessed areas.
The vent termination must not be located above any
public walkways.