Error messages – Slant/Fin SC-3 User Manual

Page 24

Advertising
background image

25

SC-3 Controller

Error Messages

The control was unable to read a piece of information stored in its memory. Because of this, the

control was required to reload the factory settings into all of the items in the ADJUST menu. The

control will stop operation until all of the items in the ADJUST menu of the control have been

checked by the user or installer.

Note: The Installer / Adv DIP Switch must be set to Adv in order to clear the error.

The control is no longer able to read the outdoor sensor due to a short circuit. In this case the

control assumes an outdoor temperature of 32˚F (0˚C) and continues operation. Locate and repair

the problem. To clear the error message from the control after the sensor has been repaired, press

either the Menu or Item button.

This error message only occurs if the External Input/Stand Alone DIP switch is set to Stand Alone.

The control is no longer able to read the outdoor sensor due to an open circuit. In this case the

control assumes an outdoor temperature of 32˚F (0˚C) and continues operation. Locate and repair

the problem. To clear the error message from the control after the sensor has been repaired, press

either the Menu or Item button.

This error message only occurs if the External Input/Stand Alone DIP switch is set to Stand Alone.

The control is no longer able to read the boiler supply sensor due to an open circuit. The control

will not operate the boiler(s) until the sensor is repaired. Locate and repair the problem. To clear

the error message from the control after the sensor has been repaired, press either the Menu or

Item button.

The control is no longer able to read the boiler supply sensor due to a short circuit. The control will

not operate the boiler(s) until the sensor is repaired. Locate and repair the problem. To clear the

error message from the control after the sensor has been repaired, press either the Menu or Item

button.

The control is no longer able to read the boiler return sensor due to a short circuit. The control will

continue to operate normally. Locate and repair the problem. To clear the error message from the

control after the sensor has been repaired, press either the Menu or Item button.

The control is no longer able to read the boiler return sensor due to an open circuit. The control

will continue to operate normally. Locate and repair the problem. To clear the error message from

the control after the sensor has been repaired, press either the Menu or Item button.

If the boiler return sensor was deliberately removed from the control, remove power from the con-

trol and repower the control to clear the error message.