13 - use, E52 e53 – Slant/Fin VSL-160C Part C User Manual

Page 10

Advertising
background image

82

13 - USE

E14

13.18.2 - Diagnostics: “E” blocking errors (continued)

“E”
Code

Blocking
description

Checks to make

Solutions

U8 return temperature
sensor short-circuited

E15

E16

E17

E18

E19

E20

E21

E22

E23

E30

E31

E32

E33

E42

E50

E51

U4 outside sensor short-
circuited

Erroneous temperature
reading.

U3 cold water temperature
or indirect water heater
temperature sensor circuit
shorted

U6 boiler temperature
sensor circuit shorted

E2prom memory damaged

Flame presence with gas
valve closed

Phase and neutral inverted

Electrical supply frequency
other than 60Hz

Ground connection is
absent

Erroneous temperature
reading.

Erroneous temperature
reading.

Erroneous temperature
reading.

Erroneous temperature
reading.

Program error

Error in the boiler tY
parameter selection

Reset button pressed too
often in a short period time

Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current
Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.14;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current

Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current

Invert phase and neutral

Check the electrical frequency of the
system.
Check if CS parameter is at 03 (see
section 17)

Check that the electrical resistance of
the sensor corresponds with the graph in
section 14.13;
check that the electrical connection cables
between the sensor and the power control
board have continuity and carry current

Check if the boiler is properly grounded

Move ON switches 7 an set again the
correct tY value (see section 17)

If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board

If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board

Replace the power control board

If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board

If the sensor resistance does not correspond, it must be
replaced;
if the electrical circuit is damaged, it must be repaired;
if the previous two cases do not apply, replace the power
control board

Replace the command and control board

Replace the gas valve

If phase and neutral are correctly wired, replace the power and
control board

If the electrical supply frequency is other than 60Hz, contact
the electric company;
if the mains frequency is 60Hz, replace the command and
control board.
Make sure that the CS parameter is at 03.

if the boiler is properly grounded, replace the power control
board

Replace the power control board

Replace the power control board

Replace the power control board

Replace the power control board

Replace the power control board

If tY value is correct, change the power control board

E52

E53

Heating fl ow switch
closed

Heating fl ow switch
open

Check if the heating pump is running.
Check if the fl ow switch contact is stuck

Check if the heating pump is running.
Check if the fl ow switch contact is
broken

The pump should not run and the contanct should open
The contact must be open

The pump should run and the contact should closed
The contact must be closed

Advertising