13 - use, L” code lock-out description controls solutions, 1 - diagnostics: “l” lock-outs (continued) – Slant/Fin VSL-160C Part C User Manual

Page 8

Advertising
background image

80

13 - USE

“L”
Code

Lock-out
description

Controls

Solutions

L18

L19

L20

L25

L32

L33

L45

L46

Program error

Flame sensed for 10
seconds, after the closure
of the gas valve

Flame sensed before
opening of the gas valve.

U1 or U6 sensor increase
its temperature too fast

Program error

Fan rotation error

Heating circuit fi lling time
longer than 10 minutes.

Check:
a - that the heating water fl ow is not too

low;

b - that the circulator pump is working

Check that the voltage to the fan is
163(±10)Vdc.

Replace the power control board

Call technical service

Call technical service

a - If temperature difference between U1 and U8 is higher than

55°F (31°C), at maximum input, the heating water fl ow rate
is too low. The heating water fl ow rate must be corrected.

b - If the pump works, replace the power control board.

Check:
a - that the heating pressure switch

setting pressure, FILL appears when
the pressure drops below 8.7 psi
(0,6 bar), and disappears when the
pressure rises above 22 psi (1.5
bar);

b - check that there are no water leaks

in the heating system.

Check:
a - that no obstructions are in the fl ue

discharge/air intake line

b - check the fl ue pressure switch

setting point, setting is 4.5 in.W.C

c - check that the electrical resistance of

the fl ue gas sensor corresponds with
the graph in section 14.13;

d - check that the electrical connection

cables between the fl ue pressure
switch, the fl ue sensor and the
power control board.

Replace the power control board

If the fan is powered with 163Vdc, replace the fan. If the voltage
to the fan is not 163 Vdc, replace the board.

a -If the heating pressure switch is not correctly set, it must be

replaced;

b - if the system has a leak, it must be fi xed.

Filling of heating circuit
repeated 16 times in 24
hours

13.18.1 - Diagnostics: “L” lock-outs (continued)

L47

Flue pressure switch
open time longer than 60
minutes

a -If ther’is an obstruction, it must be removed;
b - If the fl ue pressure switch is not correctly set, it must be

replaced;

c - If the fl ue sensor resistance does not correspond, it must be

replaced;

d - if the electrical circuit is damaged, it must be repaired;

if the previous four cases do not apply, replace the power
control board

L21

Boiler in blocking state for
more than 20 hours

Press RESET button and check the blocking error “E” on
Section 13.18.2