13 - use – Slant/Fin VSL-160C Part C User Manual

Page 5

Advertising
background image

77

13 - USE

PARAMETER DESCRIPTION

INFORMATION ON DISPLAY ITEM “2” OF FIGURE 13-1

Can be changed (see Section 13.9):
00 = thermostatic adjustment;
01 = outdoor reset;
02 = outdoor reset with room compensation;

Keep always at value of 1

Can be changed from 16°F (-9°C) to 149°F (65°C) (active only with
outdoor reset).
See section 13.10.3 for its adjustment.

Can be changed: from 1°F (1°C) to 36°F (20°C) (active only with
outdoor reset featuring room compensation)
See section 13.10.6 for its adjustment.

Can be changed:
01 = knobs presents;
00 = knobs absent.

Can be changed: 00 = display always on; any other value,
corresponds to a delay in the switching off of the display, expressed
in minutes (see also Section 13.15)

No infl uence in this kind of boiler

No infl uence in this kind of boiler

Must be maintained at 20 value

Must be maintained at 40 value

Can be changed between 1 and 54. Default value is 18 (180 sec).
Can be modifi ed only in conjunction with factory technicians.

Can be changed between 00 (function disabled) and 99 minutes.
Default value is 00 (See also section 9.1.1).

Heating service functioning mode

Reaction to external temperature

Angle fulcrum of climatic adjustment

Reduction of temperature generated by
the opening of the room thermostat

Boiler knobs’ status

Display “1” and “2” as per fi gure 13-1
energy saver

Parameter disabled for this kind of boiler

Domestic sensitivity setting

Minimum domestic setpoint during sleep
mode

Proportional band of the heating PID
modulation

Integral of the heating PID modulation

Burner Anticycling: minimum delay from
a burner light-off to the sequent light-on.
Value expressed in sec x 10

Indirect water heater priority selection:
Value expressed in minutes.

Continued