Dimensions:

Width = 17" Height = 12" Depth = 8

3

8

"

Specifications:

Weight (empty) = 21 lbs

Water content = 0.2 gallons

Piping connections = 3/4" nom. I.D. copper

Min. DHW flow = 0.3 gpm

Max. working pressure = 125 psi

Mounting to a Wall:

1. DHWG must be installed with water pipes at right or left

side of the unit (see figure 2).

2. Be sure that the wall is vertically plumb, and capable

of carrying the weight of the DHWG system and all

associated piping, when full of water. See the

specifications above.

3. The system may be mounted onto a combustible wall,

but the water piping must be kept a minimum of 1” away

from any combustible materials.

4. For stud type walls, be sure that there are studs available

in the desired location, and the appropriate fasteners are

utilized for the wood or metal stud type and weight

capacity.

5. For masonry walls, utilize anchors of the appropriate

design for the material and weight capacity.

6. Do not attempt to support the system with anchors driven

into sheetrock only.

3

DHWG Domestic Hot Water Generator

Table 1. DHWG pressure drop vs. flow

Table 2. DHWG temperature rise vs. water flow*

Figure 2.

Temp.

r

t –˚F

DHWG Flow Rate–GPM

LX-85A

Boiler

LX-90

Boiler

B-120A or LX-120

Boiler

LX-150

Boiler

B-200A

Boiler

100

80

70

60

55

1.4

1.8

2.1

2.5

2.8

1.6

2.0

2.3

2.7

3.0

2.0

2.5

3.0

3.5

4.0

2.3

3.3

4.0

4.5

5.0

2.5

3.75

4.75

5.75

6.5