DHWG Domestic Hot Water Generator

Electrical Wiring:

1. Make all wiring connections to the DHWG system as

shown in Figure 4.

2. Wire the DHWG system circulator’s junction box leads

to

the boiler’s “DHW CIRC” line voltage terminals. Use 14

gage conductors in BX or conduit, secured to the

connectors provided (See figure 5).

3. Wire the DHWG system water flow switch to the

boiler’s “DHW T-STAT” low voltage terminals. (terminal

#3 and #4 of boiler low voltage terminals, See figure 5).

4. Refer to the boiler manual’s “Electrical Wiring”

section, for proper installation of all additional wiring

necessary for the space heating system and operation

of the boiler.

System Settings:

Refer to the boiler manual’s “Boiler Control and Display

Features”, in the “Operating Instructions” section, for

setting the boiler parameters properly to operate with the

DHWG system.

1. The domestic hot water post pump time (see Table 5 of

the boiler manual) should be set for the minimum value

of 1 second, when the alternating letter indication of

“P-d” is selected.

2. The domestic hot water mode must be set for # 2

(see Table 5), when the alternating letter indication of

“d-t” is selected.

3. The priority mode must be set for 0, DHW priority with

no time limit (see Table 5), when the alternating letter

indication of “b-t” is selected.

4. Set all other parameters as appropriate for the space

heating system and operation of the boiler.

Figure 4. Wiring DHWG system to the Bobcat or Lynx boilers.