Field controls – Slant/Fin TRDV Series Venting User Manual

Page 13

Advertising
background image

TRDV SERIES

13

APPLIANCE ADAPTER INSTALLATION:
1. Apply a bead of sealant to appliance collar approx. 1” from

end of collar (Figure 20).

2. Remove all oil and grease from the inside of the appliance

adapter, and apply a bead of sealant to inside of adapter ?”

from end (Figure 20).

3. With a twisting motion, assemble the appliance adapter onto t

he appliance collar.

4. Using a mallet and block of wood, drive the adapter onto the

appliance collar, using care to avoid damaging the appliance

collar or the adapter (Figure 21).

5. Assemble adapter clamp halves using the supplied 5/16” bolts

and square nuts, and install the appliance clamp onto the

adapter and tighten securely (Figure 20).

6. Install the supplied self-drilling, self-tapping anchoring screws

through the 4 holes in the appliance clamp into the appliance

collar (Figure 21). No pilot hole is required.

7. Apply sealant to the end of the adapter and anchoring screws.

(Figure 21).

8. After testing and burner adjustments have been made, apply

sealant to the supplied 3/8” sampling port plug screw and

install the screw in the sampling port (Figure 21).

9. Maintain the following clearances to combustibles. If the

appliance collar is within 18" of combustible material, wrap

minimum 1-1/2" ceramic insulation (installer-supplied) around

the exposed portion of the termination inner pipe and

appliance adapter (Figure 25).

Figure 19

Figure 20

Figure 21

FIELD CONTROLS

REFER TO PAGE 8 FOR VACUUM RELIEF VALVE CONNECTIONS AND VENT SYSTEM PART NUMBERS

Advertising