Manual 36526F

DPG-21XX-00X Digital Controllers

Woodward

28

E

rr

o

r

Time

+E

-E

0

Integration works on

the sum of the errors

accumulated over time

The Derivative works on the

Instantaneous Rate of Change

in the amount of error

The Proportional

term's output is

unique for each

measured error


During each of the steps 3 through 6, you need to disturb the system by adding and
removing

a load from the engine to check the controller’s response to the load

transition.

START WITH SMALL LOADS.


Note that without integral, a speed error may persist after a load-on load-off transition.
Therefore, during steps 3-5 you should temporarily increase the integral to get the
engine speed back to the set speed, and then reset the integral to a lower value again
while working to find good proportional and derivative values. Repeat steps 3-7 as
needed to find a Proportional value, Integral value, and a Derivative value that work
well with a variety of overall gain values and different load transients.