COOLING CAPACITIES (cont)

48SS048

TEMP (F)

AIR ENT

COND

EVAP AIR - CFM/BF

14ЦЦ/Ц.08 I 1600ЖТ0 I

Evap Air — Ewb (F)

1800/0.11

62

67

72

62

67

72

62

67

72

fc

43 8

48 3

52 9

44 5

49 1

53 7

45 1

49 6

53 9

85

SHC

39 4

32 7

25 6

41 9

34 6

26 4

44 1

36 4

27 1

kW

4 76

4 85

4 95

4 87

4 97

5 07

4 99

5 08

5 17

TC

41 9

46 4

50 9

42 6

47 0

51 7

43 3

47 5

52 2

95

SHC

38 6

32 1

24 8

41 1

33 9

25 9

43 1

35 9

26 8

kW

5 17

5 28

5 38

5 29

5 40

5 50

5 41

5 51

5 61

tc

39 3

44 2

48 8

40 1

44 7

49 2

41 2

45 2

49 6

105

SHC

37 3

31 2

24 1

39 7

33 1

25 1

41 2

35 1

26 0

kW

5 61

5 73

5.83

5 74

5 85

5.95

5 87

5 96

6 06

TC

36 6

41 5

46 4

37 7

42 4

47 0

39 0

42 8

47 4

115

SHC

35 9

30 2

23 4

37 6

32 4

24 3

39 0

34 2

25 4

kW

6 08

6 22

6.34

6 22

6 34

6 45

6 36

6 46

6 57

48SS060

EVAP AIR - CFM/BF

TEMP (F)

AIR ENT

COND

1750/0.03 [ 2Ö0O/0.Ц4 | 225Ц/0.Ц5

Evap Air — Ewb (F)

62

67

72

62

67

72

62

67

72

tc

55 0

62 Ö'

69“4

56 3

63 1

70 5

58 2

63 9

71 3

85

SHC

52 4

43 7

34 2

56 1

46 7

35 8

58 1

49 5

37 4

kW

6 14

6 33

6 53

6 32

6 50

6 70

6 52

6 67

6 88

TC

51 8

58 8

66 2

53 6

59 6

67 3

55 6

60 2

68 1

95

SHC

51 0

42 4

33 2

53 5

45 3

34 8

55 6

48 2

36 3

kW

6 62

6 82

7 05

6 83

7 00

7 22

7 03

7 17

7 39

TC

48 7

55 1

62 9

51 0

56 0

63 9

53 Ö

56 7

64 5

105

SHC

48 7

41 1

32 1

50 9

44 0

33 7

52 8

46 9

35 3

kW

7 17

7 37

7 60

7 39

7 54

7.78

7.59

7 71

7 95

TC

45 8

52 0

59 5

48 5

52 8

60 5

50 4

53 4

60 8

115

SHC

45 8

40 0

30 9

48 4

42 8

32 6

50 3

45 6

34 1

kW

7 77

7 94

8 19

7.98

8 12

8 36

8 18

8 29

8 43

LEGEND

Bypass Factor
Entering Wet-Bulb

Total Unit Power Input
Sensible Heat Capacity, 1000 Btuh
Total Cooling Capacity, 1000 Btuh (net)

BF -
Ewb —
kW
SHC

TC -

NOTES
1 Ratings are net, they account for the effects of the indoor-fan motor

power and heat.

2 Direct interpolation is permissible Do not extrapolate
3. The following formulas may be used.

.

_ sensible capacity (Btuh)

1 10 X cfm

Wet-bulb temperature corresponding to enthalpy of air

leaving indoor coil (hi^b)

total capacity (Btuh)

4 5

X

cfm

Where hgwb = Enthalpy of air entering indoor coil

The SHC is based on 80 F edb temperature of air entering indoor
coil

Below 80 F edb, subtract (corr factor x cfm) from SHC

Above 80 F edb, add (con factor x cfm) to SHC
Correction Factor = 1 10 x (1 - BF) x (edb - 80)

t|db

*lwb

h|wb “ h ewb ~

15

Advertising