UNIT
SIZE

48SS

018

024,

030

036

042

048

060

DRY COIL AIR DELIVERY* - VERTICAL DISCHARGE

(Deduct 10% for 208 v)

230 AND 460 VOLT VERTICAL DISCHARGE

MOTOR

SPEED

E xternal St

atic Press ure (In. w

g)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Low

Watts

_

295

251

223

201

176

149

124

_

_

_

- - - - -

-

- - -

Cfm

821

817

753

665

536

343

164

High

Watts

401

376

346

322

294

272

250

229

219

_

_

^Cfm "

1334

" 1253 "

1Í28

996

816

658

461

246

167

Low

Watts

_

285

284

282

278

274

270

261

251

244

230

- - - -

- -

-

-

- - — - -

-

----

- _ - _

Cfm

798

761

727

682

634

581

525

450

371

304

Med

Watts

378

371

368

362

357

343

332

315

301

283

Cfm

-

1011

982

948

906

858

771

703

597

492

387

High

Watts

520

511

487

472

451

431

411

385

362

341

Cfm

1342

1289

1237

1181

1106

1007

892

745

610

471

Low

Watts

-

460

439

423

898

379

349

322

297

270

246

Cfm

1191

1136

1081

1005

907

795

687

579

471

349

Med

Watts

-

511

492

470

450

420

392

364

332

308

275

Cfm

-

1316

1244

1178

1104

1005

891

784

657

535

389

High

Watts

655

631

603

584

552

522

492"

459

433

398

Cfm

1541

1458

1367

1292

1178

1053

920

806

662

509

Low

Watts

637

612

587

560

536

493

455

-

-

Cfm

1500

1450

1405

1350

1290

1200

1105

~

High

Watts

790

750

700

699

639

608

574

547

Cfm

-

1750

1625

1604

1509

1421

1323

1221

1094

-

-

Low

Watts

-

847

784

746

708

646

609

563

516

-

-

Cfm

-

1995

1901

1822

1730

1580

1477

1319

1178

-

High

Watts

-

-

909

852

820

801

751

687

639

Cfm

-

-

2018

1896

1814

1729

1582

1380

1220

Low

Watts

-

970

952

928

905

880

847

804

760

-

-

Cfm

-

2075

2054

2024

1994

1945

1890

1830

1762

Med

Watts

-

-

1291

1247

1195

1076

1025

970

921

833

810

Cfm

~

-

2395

2348

2291

2164

2099

2022

1950

1827

1804

High

Watts

-

1490

1400

1312

1270

1219

1161

1104

1045

985

930

Cfm

-

2530

2475

2420

2355

2289

2223

2150

2079

2008

1932

*Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter

Deduct wet coil and filter pressure drops to obtain external static pressure available for ducting

NOTES
1 Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of

rated cooling capacity Evaporator coil frosting may occur at airflows below this point

2 Dashes indicate portions of table that are beyond the blower motor capacity or are not

recommended