Iliì]i5l 1, Cooling capacities and efficiencies – Carrier 48SS User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

!iliì]i5l

1

(Oi

Va;

48SS 024

060 3

1

1 AA

Model No.

48SS — Single Package

Gas Heating/
Electric Cooling

Nominal Cooling Capacity

018 — 1 1/2 Tons
024 — 2 Tons
030 — 2 1/2 Tons
036 — 3 Tons
042 — 3 1/2 Tons
048 — 4 Tons
060 — 5 Tons

Heat Level

040 — 40,000 Btuh
060 — 60,000 Btuh
080 — 80,000 Btuh

100— 100,000 Btuh
120—120,000

Btuh

140— 140,000 Btuh

Options

AA — Base Rail
AB — Downflow With Base Rail

Packaging

Series

V-Ph-Hz

3 — 208/230-1-60
5 — 208/230-3-60
6 — 460-3-60

COOLING CAPACITIES AND EFFICIENCIES

UNIT 48SS

NOMINAL

TONS

STANDARD

CFM

NET COOLINGt

CAPACITIES

SEERt

SOUND RATINGS**

(Bels)

018040

IV2

600

17,000

100

7.4

024040
024060

2

800

24,000

10 0

7 6

030040
030060
030080

2V2

1000

29,200

10 0

80

036060
036080
036100
036120

3

1200

36,000

10 0

8 0

042060
042080
042100
042120

31/2

1400

42,500

100

82

048080
048100
048120
048140

4

1600

47,000

10 0

8.2

060080
060100
060120
060140

5

1995

59,500

100

82

LEGEND

Bels

— Sound Levels (1

bel = 10 decibels)

db

— Dry Bulb

SEER

— Seasonal Energy Efficiency Ratio

wb

— Wet Bulb

'Air-Conditioning & Refrigeration Institute.
fRated in accordance with U.S Government DOE (Department of

Energy) test procedures and/or ARI Standard 210/240-89

"Rated in accordance with ARI Standard 270-84

NOTES:

1 Ratings are net values, reflecting the effects of circulating fan heat

Ratings are based on.

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera­
ture and 95 F db outdoor entering-air temperature

2, Before purchasing this appliance, read important energy cost and ef­

ficiency information available from your retailer

Advertising