Data ie©nt, Wet coil pressure drop, Filter pressure drop (in. wg) – Carrier 48SS User Manual

Page 18

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

fa

data ie©nt

WET COIL PRESSURE DROP

UNIT SIZE

AIRFLOW

_____ (cjiTl)

600

PRESSURE DROP

(in. wq)

0.069

018

700

0,082

800

0.102

900

0.116

600

0.039

024

700

0.058

800

0,075

900

0.088

900

0.088

030

1000

0.095

1200

0.123

1000

0.068

036

1200

0.088

1400

0.108

1600

0.123

1000

0.048

042

1200

0.069

1400

0.088

1600

0.102

1400

0.068

048

1600

0.075

1800

0.088

1700

0.082

060

1900

0.095

2100

0.108

2300

0.123

FILTER PRESSURE DROP (in. wg)

UNIT SIZE

FILTER

CFM

SIZE (in.)

500

600

700

800

900

1000

1100

1200

1300

1400 1500 1600 1700 1800 1900 2000 2100 2200 2300

018, 024

20

X

20

0.05

0.07

0.08

0.10 0.12

0,13

_

—-

_

_

_

_

030, 036

20

X

24

0.09

0.10 0.11

0.13

0.14

0.15 0.16

042

24

X

24

_

0.11 0.12

0.14 0.15

_

_

_

_

_

048, 060

24

X

30

0.09

0.10 0.110.12

0.13 0,14 0.15 0.16 0,17 0.18

18