Packaged Heating/Cooling Units

Constant Volume Application

HVAC Guide Specifications

Size Range: I V

2

to 5 Tons, Nominal Cooling

40,000 to 140,000 Btuh,
Nominal Input Heating

Carrier Model Number 48SS

Part 1 — General

1 01 SYSTEM DESCRIPTION

A Outdoor rooftop mounted, gas heating/electric cool­

ing unit utilizing a rotary, reciprocating, or scroll her­
metic compressor for cooling duty Unit shall discharge
supply air downward or horizontally as shown on con­
tract drawings Outdoor fan/coil section shall have a
blow-thru design for minimum sound levels.

1 02 QUALITY ASSURANCE

A Unit shall be rated in accordance with ARl Standards

210/240-89 and 270-84

B Unit shall be designed in accordance with UL Stand­

ard 564.

C Unit shall be UL listed and CSA certified as a total

package for safety requirements

D Roof curb shall be designed to conform to NRCA

Standards

E Insulation and adhesive shall meet NFPA 90A re­

quirements for flame spread and smoke generation

F Cabinet insulation shall meet ASHRE standard

no 62P

1 03 DELIVERY, STORAGE, AND HANDLING

A Unit shall be stored and handled per manufacturer’s

recommendations

Part 2 — Products
2 01 EQUIPMENT

A General

Factory-assembled, single-piece heating and cooling
unit Contained within the enclosure shall be all fac­
tory wiring, piping, controls, refrigerant charge (R-22),
and special features required prior to field start-up

B Unit Cabinet'

1 Unit cabinet shall be constructed of phosphated,

zinc-coated prepainted steel, capable of withstand­
ing 500 hours in salt spray

2 Cabinet panels shall be easily removed for

servicing

3 Indoor blower compartment interior cabinet sur­

faces shall be insulated with a minimum Vz-in. thick,
flexible fiberglass insulation, coated on the air side.
Aluminum foil-faced fiberglass insulation shall be
used in the entire section

C. Fans.

1 The indoor (evaporator) fan shall be 2- or 3-speed

direct-drive, as shown on equipment drawings

2 Fan wheel shall be made from steel, be double­

inlet type with forward curved blades with corro­
sion resistant finish and be dynamically balanced.

3 Outdoor (condenser) fan shall be of the direct driven,

propeller type with aluminum blades riveted to cor­
rosion resistant steel spiders, be dynamically bal­
anced, and discharge air vertically upwards and
horizontally

D Compressor:

1 Fully hermetic compressor with factory-installed vi­

bration isolation

2 Rotary compressors shall be standard on unit size

018 Reciprocating compressors shall be standard
on unit sizes 024-042 Scroll compressors shall be
standard on unit sizes 048 and 060.

E Coils

Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless copper
tubes with all joints brazed Tube sheet openings shall
be belled to prevent tube wear.

F Heating Section.

1 Induced-draft combustion type with energy saving

direct spark ignition system and redundant main
gas valve

2. Induced-draft motors shall be provided with solid-

state hall effects sensor to ensure adequate airflow
for combustion

3 The heat exchangers shall be constructed of alu­

minized steel for corrosion resistance

4 Burners shall be of the in-shot type constructed of

aluminum coated steel

5 Integrated gas control board shall provide control

of heating and simplify troubleshooting through its
built-in diagnostic function.

6. All gas piping and electric power shall enter the unit

cabinet at a single location

G. Refrigerant Components-

Refrigerant components shall be of the Acutrol”' feed
system type

H. Filter section shall consist of field-installed, throw­

away, 1-in. thick fiberglass filters of commercially avail­
able sizes

I. Controls and Safeties

1 Unit Controls.

a Unit shall be complete with self-contained low-

voltage control circuit.

2 Safeties.

Compressors shall incorporate a solid-state com­
pressor protector which provides reset capability