Carrier 48SS User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

H

SERIES 311, 511, AND 611

UNIT SIZE 48SS

018040

024040

024060

030040

030060

030080

036060

036080

036100

036120

NOMINAL CAPACITY (ton)

IVa

2

2

2'/2

2Va

2V2

3

3

3

3

OPERATING WEIGHT (lb)

Without Base Rail

272

303

315

320

324

324

336

336

348

348

With Optional Base Rail

296

327

339

344

356

356

360

360

372

372

COMPRESSORS

Rotary

Reciprocating

Quantity

1

REFRIGERANT (R-22)

.. -

... ....

Charge (lb)

2 60

2 75

2 75

3 40

3 40

3 40

4 30

4 30

4 30

4.30

REFRIGERANT METERING DEVICE

Acutrol"' Device

Orifice ID (in.)

030

030

030

030

030

030

.032

032

032

032

CONDENSER COIL

Rows...Fins/in

1. 17

1. 17

1. 17

2 17

2. .17

2. .17

2. .17

2. .17

2. 17

2. .17

Face Area (sq ft)

5 95

5 95

5 95

5 95

5 95

5 95

5 95

5 95

5 95

5 95

CONDENSER FAN

Nominal Cfm

1700

1700

1700

1900

1900

1900

1900

1900

1900

1900

Diameter (in.)

18

18

18

18

18

18

18

18

18

18

Motor Hp (Rpm)

'/s (850)

Ve

(850)

Ve

(850)

Ve

(850)

Ve

(850)

Ve

(850)

'A

(1050)

'A

(1050)

V4 (1050)

'/i (1050)

EVAPORATOR COIL

Rows...Flns/ln

3 15

3 . 15

3 15

3 15

3 15

3 15

3 15

3 15

3 15

3 15

Face Area (sq ft)

1 83

2 29

2 29

2 29

2 29

2 29

3 06

3 06

3 06

3 06

EVAPORATOR FAN

Direct Drive

Nominal Airflow (Cfm)

600

800

800

1000

1000

1000

1200

1200

1200

1200

Size (in )

10 x 10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

FURNACE SECTION*

Burner Orifice No. (Qty. .drill size)

Natural Gas

1 32

1 32

2 38

1 32

2 38

2 32

2 38

2 32

3 36

3 32

Burner Orifice No. (Qty...drill size)

Propane Gas

1 41

1 41

2 46

1 41

2 46

2 42

2 46

2 42

3 44

3 42

RETURN-AIR FILTERS (in.)t

Throwaway

20

X

20

20

X

20

20

X

20

20

X

24

20

X

24

20

X

24

20

X

24

20

X

24

20

X

24

20

X

24

UNIT SIZE 48SS

042060

042080

042100

042120

048080

048100

048120

048140

060080

060100

060120

060140

NQMINAL CAPACITY (ton)

3'/2

3'/2

3V2

3V2

4

4

4

4

5

5

5

5

QPERATING WEIGHT (lb)

Without Base Rail

375

375

387

387

414

426

426

426

453

465

465

465

With Qptional Base Rail

399

399

411

411

438

450

450

450

477

489

489

489

CGMPRÉSSORS

Reciprocating

Hermetic Scroll

Quantity

REFRIGERANT (R-22)

Charge (lb)

5 20

5 20

5 20

5 20

6 50

6 50

6 50

6 50

7 00

7 00

7 00

7 00

REFRIGERANT METERING

Acutroi'

Device

DEVICE

Qrifice ID (in.)

034

034

034

034

030

030

030

030

030

030

030

030

CQNDENSER CQIL

Rows.. Fins/in.

2. .17

2. 17

2. .17

2. .17

2. 17

2 17

2. 17

2. 17

2 17

2. 17

2. 17

2. 17

Face Area (sq ft)

7 04

7 04

7.04

7,04

8 67

8 67

8 67

8 67

8 67

8 67

8 67

8 67

CQNDENSER FAN

Nominal Cfm

1900

1900

1900

1900

2400

2400

2400

2400

2400

2400

2400

2400

Diameter (in.)

18

18

18

18

20

20

20

20

20

20

20

20

Motor Hp (Rpm)

'A

(1050)

'/4 (1050)

'A

(1050)

'/4 (1050)

Ve

(1 050)

Ve

(1050)

'/3

(1050)

Ve

(1050)

'/3

(1050)

Ve

(1050)

Ve

(1050)

Ve

(1050)

EVAPDRATQR COIL

Rows...Fins/in

3 15

3 15

3 .15

3 15

3. 15

3. 15

3. 15

3. 15

4. 15

4. 15

4. 15

4. 15

Face Area (sq ft)

3 33

3 33

3 33

3 33

4 44

4 44

4 44

4 44

4 44

4 44

4 44

4 44

EVAPORATOR FAN

Direct Drive

Nominal Airflow (Cfm)

1400

1400

1400

1400

1600

1600

1600

1600

1995

1995

1995

1995

Size (In.)

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

10

X

10

FURNACE SECTION*

Burner Orifice No.

(Qty. drill size)
Natural Gas

Burner Orifice No.

2 38

2 32

3 36

3 32

2 32

3 36

3 .32

3 30

2 32

3 36

3 32

3 30

(Qty...drill size)
Propane Gas

2 46

2 42

3 44

3 42

2 42

3 44

3 42

3 40

3 42

3 44

3 42

3 40

RETURN-AIR FILTERS (in.)t

Throwaway

24

X

24

24

X

24

24

X

24

24

X

24

24

X

30

24

X

30

24

X

30

816**

24

X

30

24

X

30

24

X

30

960**

•Based on altitude of 0-2000 feet

tRequired filter sizes shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated

cooling airflow or the heating airflow at a velocity of 300 ft/min for throwaway type or 450 ft/min for high-capacity
type Air filter pressure drop for non-standard filters must not exceed 0 08 in wg

**Sq inch Filter is mounted external to unit

Advertising