Table ЗА — Units 38AH044-084 Physical Data — 50/60 Hz (English)

38AH

044

054

064

074

084

OPERATING WEIGHT WITH Cu-AI

REFRIGERANT (Approx) — Lb Cu-Cu

3259
3547

3309
3597

3565
3998

3812
4229

4057
4735

SHIP WEIGHT WITH COIL PROTECTION ONLY

(Approx) — Lb Cu-AI

Cu-Cu

3250
3538

3290
3578

3530
3963

3780
4197

4000
4678

TYPICAL OPERATING REFRIGERANT

Charge (Approx) — Lb
Qty of Circuits

Std

Opt

62

2

1

72

2

1

R-22

88

2

1

104

2

1

130

2

1

COMPRESSOR Type...Rpm

(Qty Cylinder) Compressor*
Model No. 06E
(Qty Cylinder) Compressor*
Model No. 06E
Oil Charge (Pt)

Capacity Control Stepsf

Reciprocating Semi-Hermetic

1750 @ 60 Hz; 1458 @ 50 Hz

Std

(4)A1

(4) B1

(4) A1

(6) B1

(6) A1

(6) B1

(6) A1

(6) B1

(6)A1

(6) B1

Std

250

250

250

265

265

275

275

299

299

299

Opt

(4)A1

(4) A2

(6) A1

(4) A2

(6) A1

(6) A2

(6) A1

(6) A2

(6)A1

(6) A2

Opt

250

250

265

250

275

265

299

275

299

299

Std

17

17

17

21

21

21

21

19

19

19

Opt

17

17

21

17

21

21

19

21

19

19

CONDENSER FANS (6 Blade) — 60 Hz

Qty...Dla (In.)
Ainlow (Cfm)
Speed (Rpm)
Total Power (kW)

4. .30

35,000

1140

6.2

52,000

6 .30

I

1140

93

51,000

CONDENSER FANS (6 Blade) -

Qty...Dia (in.)
Airflow (Cfm)
Speed (Rpm)
Total Power (kW)

■50 Hz

4. ,30

35,000

950

62

6 .30

52,000 I 51,000

950

93

CONDENSER COIL

Enhanced Co pper Tubes, Aluminum Lanced Fin

Rows...Fins per in.

2...17

2...17

3...17

2...19

3 .17

Face Area (sq ft)

80.5

80.5

80.5

116.7

1167

Storage Capacity (Lb per Circuit) at 120 F

35

35

55

55

80

CONNECTIONS

Suction, ODF (in.)**

2Va

Liquid, ODF (in.)**

%

Hot Gas Bypass, ODF (in.)

¥e

Table 3B — Units 38AH044-084 Physical Data — 50/60 Hz (SI)

38AH

044

054

064

074

084

OPERATING WEIGHT WITH

Cu-AI

1478

1501

1617

1729

1840

REFRIGERANT (Approx) — Kg

Cu-Cu

1609

1632

1813

1918

2148

SHIP WEIGHT WITH COIL PROTECTION ONLY

(Approx) — Kg

Cu-AI

1474

1492

1601

1715

1814

Cu-Cu

1605

1623

1798

1904

2122

TYPICAL OPERATING REFRIGERANT

R-22

CHARGE (Approx) — Kg

28 1

32 7

39 9

47 2

58 9

Qty of Circuits

Std

2

2

2

2

2

Opt

1

1

1

1

COMPRESSOR Type...R/s

Reciprocating Semi-Hermetic

29.2 @ 60 Hz; 24.3 @ 50 Hz

(Qty Cylinder) Compressor*

Std

(4) A1

(4)B1

(4) A1

(6) B1

(6) A1

(6) B1

(6) A1

(6) B1

(6) A1

(6) B1

Model No. 06E

Std

250

250

250

265

265

275

275

299

299

299

(Qty) Cylinder) Compressor*

Opt

(4)A1

(4) A2

(6) A1

(4) A2

(6) A1

(6) A2

(6)A1

(6) A2

(6)A1

(6) A2

Model No. 06E

Opt

250

250

265

250

275

265

299

275

299

299

Oil Charge (L)

Std

8 0

80

80

9 9

9 9

99

99

90

9.0

90

Opt

80

80

99

80

9.9

99

90

99

90

90

Capacity Control Stepsf

Z;

CONDENSER FANS (6 Blade) — 50 Hz

Qty...Dia (mm)

4.. 762

6

762

Airflow (L/s)

16 500

24 500

24 100

Speed (R/s)

15.8

15.8

Total Power (kW)

62

93

CONDENSER FANS (6 Blade) — 60 Hz

Qty...Dia (mm)

4.. 762

6. 762

Airflow (L/s)

16 500

24 500

24 100

Speed (R/s)

19.0

19.0

Total Power (kW)

62

93

CONDENSER COIL

Enhanced Copper Tubes, Aiuminum Lanced Fin

Rows...Fins per m

2.. 669

2.. 669

3,. 669

2 .. 782

3...669

Face Area (sq m)

7.48

7.48

7.48

10 84

10 84

Storage Capacity (Kg per Circuit) at 48.9 C

16

16

25

25

36

CONNECTIONS

Suction, ODF (in.)**
Liquid, ODF (in.)**
Hot Gas Bypass, ODF (in.)

2Va

Ve

%

LEGEND

Cu-AI

— Copper tubes with aluminum fins

Cu-Cu

— Copper tubes with copper fins

ODF

— Outside Diameter, Female

Opt

— Optional Single-Circuit Units

Std

— Standard Dual-Circuit Units

•Compressor A1 is lead on standard and optional single-circuit units

tCapacity control steps listed are for constant-volume units with no accesso­

ries Refer to Table 19A or 19B, page 46, for additional system capacity

information

**For single-circuit units, suction ODF is 2% in. (66 7 mm) and liquid ODF is

IVs in (28.6 mm)

Single circuits have a factory-installed manifold; no

field modification is required.

NOTES:

1 Certified dimensional drawings available on request

2 Equivalent connection values in mm are as follows;

in.

mm

%

15.9

%

22 2

2Ув

54 0

10