SIGHT GLASS

THERMOSTATIC

EXPANSION VALVES

DRIER

OPTION B
DUAL FILTER
DRIER ARRANGEMENT

SIGHT GLASS

LOCATION A

SIGHT GLASS
LOCATION B

THERMOSTATIC

EXPANSION
VALVES

Fig. 12 — Required Location of Soienoid Vaives and Recommended Fiiter Drier and

Sight Giass Locations for 38AH044-084 Optionai Single-Circuit Units

u

\

■ CONDENSING

\

------- 1—UNIT

3 FT MAX (914 mm)

LEGEND

A

— Pipe A, Suction Riser, without Trap

B

— Pipe B, Suction Riser with Trap

C

— Suction Line to Condensing

Unit

D

— Pipe D, Suction

Riser Short Lift

RED.

— Reducer

STR

— Street

NOTES-
1

Short riser, pipe D, is used when routing suction iine to condens­

ing unit connection See table at right

2. See Tables 7A, 7B, 9A, and 9B for values of A, B, and C.

PIPE D DIAMETER

UNIT

38AH

Dual Circuit*

Singie Circuit*

A

B

in.

mm

in.

mm

in.

mm

044

1%

41

1%

41

21/8

54

054

1%

41

1%

41

21/8

54

064

1%

41

21/8

54

21/a

54

074

21/0

54

21/8

54

21/8

54

084

21/8

54

21/8

54

2%t

67t

094, 104

21/8

54

21/8

54

124, 134

2%

67

2%

67

‘Maximum iength of riser is 3 ft (914 mm).
tDouble suction riser required if accessory

instaiied

unioader is fieid

Fig. 13 — Double Suction Riser Construction

15