Carrier 38AH044-134 User Manual

Page 25

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 11 — Electrical Data — 50/60 Hz (Units 38AH094,104)

UNIT

38AH

VOLTAGE

DESIGNATION

NAMEPLATE

V-Ph-Hz

SUPPLY

VOLTAGE*

MCA

MOCP

ICF

COMPRESSORt

A1

A2

B1

B2

Min

Max

RLA

LRA

RLA

LRA

RLA

LRA

RLA

LRA

094

500

208/230-3-60

187

253

398 5

500

897

106.4

506

67.9

345

147.7

690

600

460-3-60

414

506

183 1

225

443

46.8

253

34.6

173

65.4

345

100

575-3-60

518

633

160.9

200

366

40.4

176

28 8

120

57.1

276

200

380-3-60

342

418

209.1

250

493

52 6

280

34.6

191

78.8

382

900

380/415-3-50

342

440

183.6

225

444

46.8

280

34 6

173

65.4

345

300 (PW)

346-3-50

325

380

212 9

250

343

53 8

168

33.3

115

79.5

■229

104

500

208/230-3-60

187

253

399.4

450

722

89 7

446

67 9

345

89.7

446

89 7

446

600

460-3-60

414

506

196.3

225

361

43.6

223

34 6

173

43 6

223

43 6

223

100

575-3-60

518

633

168.0

200

286

36.5

164

28.8

120

36 5

164

36 5

164

200

380-3-60

342

418

205 9

250

396

45.5

247

34 6

191

45 5

247

45.5

247

900

380/415-3-50

342

440

196.7

225

363

43.6

223

34 6

173

43.6

223

43.6

223

300 (PW)

346-3-50

325

380

205 6

250

298

44 9

148

33 3

229

44 9

148

49 9

148

LEGEND

— Not Applicable

FLA

— Full Load Amps

ICF

— Maximum Instantaneous Current Flow During Starting (The

point in the starting sequence where the sum of the LRA
for the starting compressors, plus the total RLAforall run­

ning compressors, plus the FLA for all running fan mo­

tors is maximum)

kcmil

— Thousand Circular Mils

LRA

— Locked Rotor Amps

MCA

— Minimum CircuitAmps (used for sizing, complies with Na­

tional Electrical Code [NEC] [ U S A Standard],

section 430-24).

MOCP

— Maximum Overcurrent Protection (used for sizing

disconnect, compiies with NEC [U.S A Standard],
section 440-22)

RLA

— Rated Load Amps

‘Units are suitable for use on electrical systems where voltage sup­

plied to unit terminals is within listed minimum to maximum limits

tAII compressors are across-the-line start only except 346-V, 3-ph,

50-Hz units.

NOTES.
1 Maximum allowable phase imbalance: voltage - 2%; amps -10%

2. Maximum incoming wire size for terminal block is 500 kcmil
3. For units 38AFI094 and 104 compressor model numbers, see table

below

UNIT 38AH

094

104

CKT

A1

A2

B1

A1

A2

B1

B2

MODEL

NO. 06E

-275

-250

-299

-265

-250

-265

-265

25