Carrier 38AH044-134 User Manual

Page 34

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

MODUPANEL

POWER
SUPPLY

115-1-GO

OR 220 1-50

--- 1- —---------1

-CEy

>|—1

10 AMP

'

AHMS-

IFC-AUX

(-------------

1 f —

-of 1-0-

! 1

' r*

-O'l H>-

i

NOTES:

1

Factory wiring is in accordance with NEC Field modifications or ad­

ditions must be in compliance with all applicable codes

2 Wiring for field power supply musf be rated 75 C minimum. Use cop­

per, copper-clad aluminum, or aluminum conductors Maximum in­
coming wire size for each ferminal block is 500 kcmil

3. Terminal blocks TBS, TB4, TBX1, and TBX2 are for external field

control connections. Control connections are to be class 1 wiring

4

Field-supplied components (IFC, LLS-A1, A2, B1, and B2) must have

a maximum sealed coil rating of 30 va each (0 25 amp at

120 vac, 0 13 amp at 230 vac). ARMS IFC-AUX contact must have

minimum pilot duty rating of 325 va each (2 7 amps at 120 vac,

1 4 amps at 230 vac)

5

Replacement of factory wires must be with type 105 C wire or its

equivalent.

6

Field-supplied liquid line solenoid valves installed at the evaporator

are required on all units

7 Control has 25 va of power available for field-installed accessories.

(208/230V)

PARALLEL CONDUCTORS

(ALL VOLTAGES)

SINGLE-ENTRY POWER

LEGEND

ARMS

— Air Handler Motor Starter

SDR —

Solenoid Drop Relay

AUX

— Auxiliary

TB —

Terminal Block

C

— Compressor Contactor

TBX —

Terminal Block for Variable

FU

— Fuse

Air Volume Units

GND

— Equipment Ground

TWl —

Timer Motor

IFC

— Indoor Fan Control

TR —

Timer Relay

kcmil

— Thousand Circular Mils

TRAN —

Transformer

LLS

— Liquid Line Solenoid

U

Unloader Solenoid

NEC

— National Electrical Code

( U S A Standard)

Factory Wiring

Field Wiring

Fig. 26 — Field Wiring, Single ModuPanel™ Control, Unit 38AH094

34