V I E W S - 5

TOP VIEW OF CONTROL BOX SHELF

WITH FIELD POWER SUPPLY CONNECTIONS

SCALE 1:10

(32) MT6 HOLES

17/32' DIA.

[13mtn]

J HINGED ACCESS

\

PANEL '

(CONTROL SIDE)

, 1 TYPICAL

•1 BOTH ENOS

HINGED ACCESS ,

> PANEL

(POWER SIDE)

TYPICAL

BOTH ENDS

■ Isl"

RELIEF VALVES LOCATED ON

THE COMPRESSORS ARE EQUIPPED

WITH A 3/8' 5AE FLARE FOR

FIELD CONNECTION

-1 -4 7/8'

1

c- 1 /'i' (42ВямпЗ

I -b I/2 MTG HOLES

НТО HOLES

I -3/4'

СЭ23вя|]

ИТ6 HOLES

-

20'-6

1

/

8

'-

[6253inm]

BASE OVERALL

Chart 1, Field Power Supply Connections

NOTES;

1

UNIT

38AH

VOLTAGE

Hz

DIAMETER —

in. (mm)

QUANTITY

134A

208/230

60

ЗУ8 (92)

1

460, 575, 380

60

2Уг (63)

1

346, 380/415

50

ЗУв (92)

1

134B

208/230

60

2Vi

(63)

2

460, 575

60

2Уг (63)

1

380

60

ЗУв (92)

1

346, 380/415

50

ЗУв (92)

1

LEGEND

C

— Copper Fin Coils

MTG

— Mounting

SAE

— Society of Automotive Engineers

8

9

10

The approximate operating weight of the unit is;

38AH-134—

7507 ib (3405 kg)

38AH-134-C

8357 ib (3791 kg)

Unit must have ciearances for airfiow as foliows;

Top — Do not restrict in any way

Ends — 5 ft [1524 mm]
Sides — 6 ft [1829 mm]
Mounting hoies may be used to mount unit to concrete pad They are not

recommended for mounting unit to spring isoiators.

One

ЗУа"

(92-mm) dia hoie is recommended for single-entry power into

Module 134A and 208/230-v units Single entry power into Module 134B is
not recommended

Circled numerals in Top View refer to condenser fans by position

If spring isolators are used, a perimeter support channel between the as­

sembled unit and the isolators is recommended Do not support each mod­

ule separately
Each module of the unit must be rigged into position separately. The unit

must not be rigged after modules have been connected.
Suction and liquid connections can exit on either side of the unit

Field power supply connections are required for each module

See Table 1A or 1В for rigging center of gravity (Dimensions K,L,X,Y). See

Table 2A and 2B for A-D corner weights.

Fig. 6 — Dimensions — Unit 38AH134