Carrier 38AH044-134 User Manual

Page 32

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

380V, 380/415V,

34SV ONLY

4,

4

ЯВ

ЭВ

OE

Ш

-L.

OS

ЕШ

1

FIELO POWER

I I

PARALLEL CONOUCIORS

t20B/Z30V>

_l__________ I_________l_l________ l_

I _ _ je^ 0iSC0N»ecT_________________j

3BAH04A-084 (ALL V0LTAGE51

SINGLE ENTRY POWER

NOTES:

1. Factory wiring is in accordance with NEC; field modifications or additions must be in com­

pliance with all applicable codes.

2. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad alu­

minum, or aluminum conductors. Maximum incoming wire size for each terminal block is

500 kcmil.

3. Terminal blocks TBS and TB4 are for external field control connections. Control connections

are to be class 1 wiring.

Field-supplied components (IFC, LLS-A, and LLS-B) must have a maximum sealed coil

rating of 30 va each (.25 amp at 120 vac, 13 amp at 230 vac). AHMS IFC-AUX must have

a minimum pilot duty rating of 200 va (1.7 amps at 120 vac, 0.9 amps at 230 vac) each,

5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.

7 Units have 175 va of power available for field-installed accessories.

4.

Fig. 24 — Field Wiring, Single ModuPanel™ Control, 38AH044-084 Dual-Circuit Units