Table 7A — Refrigerant Piping Requirements, 38AH044-104 Dual-Circuit Units — 50 Hz

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)

UNIT

15-25

25-50

50-75

75-100

100-150

150-200

38AH

(4.6-7.6)

(7.6-15.2)

(15.2-22.9)

(22.9-30.5)

(30.5-45.7)

(45.7-61.0)

L

S

L

S

L

s

L

s

L

s

L

s

044

Ckt A

%

1%

%

1%

%

1%

%

2У8

Va

2Уе

Va

2У8

Ckt В

%

1%

%

1%

Va

1%

Va

2У8

Va

2Va

Va

2У8

054

Ckt A

%

1%

Va

1%

Va

1%

Va

2Уб

Va

2Va

Va

2У8

Ckt В

%

Wa

Va

1%

Va

2У8

Va

2Уа

^Va

2Va

1У8

2%*t

064

Ckt A

%

Wa

Va

1%

Va

2yst

Va

2Va\

V/a

2Va\

1У8

2%”

Ckt В

%

1%

Va

2У8

Va

2Ув

Va

2Va

V/a

2%*

' 1У8

2%’

074

Ckt A

%

1%

Va

2Уа

Va

2Ув

Va

2Va

^Va

2%t

1У8

2%t

Ckt В

%

2Ув

Va

2Уб

1У8

2Ув

1У8

2%

V/a

2%

1У8

2%

084

Ckt A

%

2Va

Va

2Ув

1У8

2Ув

1У8

2%t

1У8

1У8

2%t

Ckt В

%

2Va

Va

2Ув

1Ув

2У8

1Уа

2%

1У8

2%

1У8

2%

094

Ckt A

%

2Va

IVe

2Ув ^

1У8

2%”

1У8

2%”

1У8

2%”

1%

ЗУв”

Ckt В

%

2Va

%

2Уе

1У8

2У8

1У8

2¥8*t

1У8

2%*t

1У8

2%’t

104

Ckt A

%

2Va

Va

2Ув

1У8

2Уа

1У8

2%”

1У8

2У8**

1%

ЗУе”

Ckt В

%

2Va

1У8

2Ув

1У8

2%

1У8

2Va

1%

2%

1%

ЗУ8”

i.

LEGEND

CV

— Constant Volume

L

— Liquid Line

S

— Suction Line

VAV

— Variable Air Volume

’Double suction riser required on units with field installed unloader

on circuit B compressor if condensing unit is elevated above

evaporator.

TDouble suction riser required on units with field installed unloader

on circuit B compressor if condensing unit is elevated above
evaporator.

’’Double suction riser required on all unit configurations if condens­

ing unit is elevated above evaporator

NOTES-

1

Addition of 2 unloaders to circuit B compressor is not

recommended

2. 38AH094 and 38AH104 piping sizes apply only to factory sup­

plied unit configurations They do NOT take into account any field
installed unloaders

3

Piping sizes are based on unit operation above 40 F (4 4 C) satu­

rated suction temperature (SST) When operating below 40 F
(4 4 C), refer to Carrier System Design Manual, E20-II piping de­
sign program, or ASHRAE Handbook to select proper line sizes

4

Pipe sizes are based on the total linear length shown for each

column, plus a 50% allowance for fittings

5.

Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1 1 C) at nominal rating conditions. Higher pressure drop

design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency

6

Double suction risers may be required if condensing unit is el­

evated above the evaporator See footnotes and double suction
riser table below

7

Refer to Carrier System Design Manual or to E20-II design

programs for further information on selecting pipe sizes for split
systems

8

All pipe sizes are OD inches Equivalent sizes in millimeters

follow

in.

mm

Va

159

Va

22 2

V/a

28 6

V/a

34 9

V/a

41 3

2Va

54 0

2Va

66.7

ЗУ8

79 4

ЗУ8

92 1

Table 7B— Refrigerant Piping Requirements for Double Suction Risers,

38AH054-104 Dual-Circuit Units — 50 Hz

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)

UNIT

50-75

75-100

100-150

150-200

38AH

15.2-22.9)

(22.9-30.5)

30.5-45.7)

45.7-61.0

A

В

C

A

В

С

А

В

С

А

В

С

054

Ckt A

Ckt В

___

___

___

___

___

V/a

2Уа

25/8

064

Ckt A

1%

V/a

2У8

V/a

V/a

2Ув

15/8

15/8

2У8

V/a

2Уа

25/8

Ckt В

15/8

2Уа

25/8

V/a

2Уа

25/8

074

Ckt A

Ckt В

___

___

___

___

___

15/8

2Уа

25/8

V/a

2Уа

25/8

084

Ckt A
Ckt В

___

___

V/a

2У8

25/8

15/8

2Уа

25/8

V/a

2Уа

25/8

094

Ckt A

V/a

2Vs

2%

V/a

2Уз

25/8

15/s

2Уа

25/8

V/a

25/8

ЗУз

Ckt В

V/a

2Ув

25/8

15/8

2Уа

25/8

V/a

2У8

25/8

104

Ckt A

V/a

2Уе

25/8

15/8

2Уа

25/8

V/a

25/8

ЗУб

Ckt В

V/a

25/8

ЗУ8

LEGEND

— Not Required

Pipe A

— Suction Riser Without Trap

Pipe B

— Suction Riser With Trap

Pipe C

— Suction Line to Condensing Unit

NOTES:

1 See Refrigerant Piping Requirements table at top of page to de­

termine need for double suction risers

2 Pipe sizes are based on the total linear length, shown for each

column, plus a 50% allowance for fittings.

3.

4.

Suction and liquid line sizing is based on pressure drop equivalent

to 2 F (1 1C) at nominal rating conditions. Higher design pressure

drop criteria may allow selection of smaller pipe sizes but at a pen­

alty of decreased system capacity and efficiency.
Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split

systems
All pipe sizes are OD inches. See Table 7A notes for metric

equivalents

Refer to Fig. 13 for double suction riser construction

17