background image

DISCHARGE

CYLINDER

GAS THERMOSTAT HEADS

OIL PRESSURE SWITCH AND
CAPACITY CONTROL

PRESSURE SWITCH CAPILLARIES

MUFFLER

FAN CYCLING
PRESSURE SWITCR

DISCHARGE

GAS

THERMOSTAT

PRESSURE

RELIEF

VALVE

NOTE: Units 38AH044-084 and 38AH124,134 compressors are pan
mounted Units 38AH094 and 104 compressors are mounted on rails.

MOUNTING

SPRING

(HIDDEN)

Fig. 29 — 06E Compressors, Typical

Preliminary Checks

1. Ensure that compressor service valves are backseated.

2. Verify that each compressor on units 38AH044-084, 124,

and 134 floats freely on its mounting springs. Verify that
each compressor on units 38AH094 and 104 floats freely

on its rails.

3. Check that electric power supply agrees with unit name­

plate data.

4. Verify that compressor crankcase heaters are securely in

place.

5. Check that compressor crankcase heaters have been on at

least 24 hours.

6. Note that compressor oil level is visible in the sight glass.

7. Recheck for leaks using same procedure as previously out­

lined in Step 3 — Make Refrigerant Piping Connections,

page 13

8. If any leaks are detected, evacuate and dehydrate as pre­

viously outlined in Step 3 — Make Refrigerant Piping
Connections, page 13.

Proliminary Oil Charge — Each compressor is fac­

tory charged with oil (see Table 3A, 3B, 4A, or 4B). When
oil is checked at start-up, it may be necessary to add or re­
move oil to bring it to the proper level. One recommended
oil level adjustment method is as follows:

ADD OIL — Close suction shutoff valve and pump down

crankcase to 2 psig (14 kPa). (Low-pressure cutout must be

jumped.) Wait a few minutes and repeat until pressure re­

mains steady at 2 psig (14 kPa). Remove oil fill plug above
the oil level sight glass, add oil through plug hole, and re­
place plug. Run compressor for 20 minutes and check oil

level.

IMPORTANT: For units with 2 compressors per re­
frigeration circuit, both compressors must be running
to adjust the oil level. Two oil level equalizer lines be­
tween compressors distribute the oil to each
compressor.

NOTE: Use only Carrier approved compressor oil. Ap­
proved sources are: Petroleum Specialties Inc. (Cryol I50A),
Texaco, Inc. (Capella WF-32-150), and Witco Chemical Co

(Suniso 3GS). Do not reuse oil that has been drained out, or
oil that has been exposed to atmosphere.
REMOVE OIL — Pump down compressor to 2 psig

(14 kPag). Loosen the Vi-in. (6.4-mm) pipe plug at the com­

pressor base and allow the oil to seep out past the threads of

the plug.

NOTE: The crankcase will be slightly pressurized. Do not
remove the plug, or the entire oil charge will be lost.

Small amounts of oil can be removed through the oil pump

discharge connection while the compressor is running.

38