OPERATION

(jo

Section 2 - Operation

Guardian Liquid-cooled 8 kW Generators

2.1

CONTROL CONSOLE COMPONENTS

The components of a liquid-cooled generator con­

trol console (Figure 2.1) are as follows:

Figure 2.1 - Control Console

# 2.1.5 HGURMETER

♦ 2.1.1 AC VOLTIVI EIER

The voltmeter displays generator AC output voltage

during operation. Voltage is regulated by a solid-
state voltage regulator and is proportional to AC
frequency. Refer to your unit's DATA PLATE for

rated AC voltage.

4 2.1.2 AC AMMETER

This indicates current draw of connected electrical

loads during operation. DO NOT EXCEED YOUR
UNIT’S RxCTED MAXIMUM CONTINUOUS CUR­
RENT. Refer to th,e unit DATA PLATE.

# 2.1.3 AC FREQUENCY METER

This indicates generator AC output frequency in
Hertz (cycles per second). Frequency is proportion­

al to engine speed. Units vlth a four-pole rotor sup­
ply 60 Hertz at 1,800 rpm. The frequency reading

with no electrical loads connected (no-load condi­
tion) should be between 61-6.3 Hertz. With full
rated wattage/amperage load applied to the gener­

ator, frequency should not droop below approxi­
mately 58 Hertz.

♦ 2.1.4 DC VOLTMETER

The generator is equipped with a belt-driven DC

alternator, which maintains batten/ state of charge

when the engine operates. The control module

assembly also incorporates a triclde charge circuit
that maintains battery state of charge during non­
operating periods. Battery voltage should read
approximately 12.5 to 14.5 volts DC. A low battery

voltage indicates the battery is discharging.

This indicates the time the engine-generator has

operated, in hours and tenths of hours. Use the

hourmeter along with the periodic maintenance

schedule for your generator set.

» 2.1.6 AUTO/OFF/MANUAL SWITCH______________

See Section 2.3.

» 2.1.7 FAULT INDICATOR LAMP___________________

This lamp goes ON when one or more of the following

engine faults occurs and when engine shuts down.

<> Low oil pressure « High coolant temperature
® Low coolant level ® Overcrank
» Overspeed

♦ 2.1.8 30-AiVIP FUSE

This fuse protects the contrcd console’s DC control

circuit against electrical overload. If the fuse has
melted open because of an overload, engine crank­
ing and start-up cannot occur. Should you need to
replace the fuse, use only an identical 30-amp
replacement fuse.

» 2.1.9 VOLTAGE-PHASE SELECTOR SWITCH

This switch permits you to select either line-to-llne

or line-to-neutral voltage and amperage readings
on the console AC voltmeter and ammeter.

♦ 2.1.10 SET EXERCISE TIME SWITCH______________

This switch allows you to program the generator to

start and exercise automatically.

4 2.1.11

MAIN

CIRCUIT BREAKER___________________

The generator’s main circuit breaker is included

with the unit as shipped from the factory. See

“Main Circuit Breaker." Section 1.5 (Page 5), for the
appropriate breaker.

2.2

PREPARATION BEFORE START-UP

Before starting the generator, check that oil,
coolant

and

fuel

levels

are

correct

(see

“Specifications,” Section 1.7, Page 6).

2.3

USING THE AUTO/OFF/MANUAL
SWITCH

♦ 2.3.1 "AUTO" POSITION

vSelecting this switch position activates fully automat­
ic system operation. It also allows the unit to start
and exercise the engine every seven days with the set­
ting of tire exercise timer (see Section 2.7, Page 10).