Section 4 — Troubleshooting

Guardian Liquid-cooled 8 kW Generators

TROUBLESHOOTING

4.1 TROUBLESHOOTING GUIDE

PROBLEM

CAUSE

CORRECTION

The engine will not crank.

1. Fuse blown

2. Loose, corroded or defective

battery cables

3. Defective starter contactor
4. Defective starter motor

5. Dead Battery

1. Replace fuse.

2. Tighten, clean or replace

as necessary.

3. *
4. *

5. Charge or replace battery.

The engine cranks but
will not start.

1. Out of fuel

2. ' Defective fuel solenoid (FS)
3. Open #14 wire from

engine control board

4. Dirty/Blocked air filter

5. Amto/Off/Manual Switch

in OFF position

1. Replenish fuel.

2. *
3. *

4. Clean or replace as required.

5. Reset to AUTO or IvLwMUAL.

The engine starts hard

and runs rough.

1. Air cleaner

plugged or damaged

2. Dlrty/Blocked air filter

1. Check, clea.n or replace air cleaner.

2. Clean or replace as required.

The engine starts, but then

shuts doLTO.

1. Engine oil level low

2. Defective low oil

pressure switch

3. Defective high temperature

switch

4. Defective control board
5. Low coolcmt level

6. Defective low coolant switch
7. Engine temperature high
8. Loss of AC sensing to

control boa.rd

1. Check oil and add oil as needed.

2 *

O .1.

o.

4. *
5. Check coolant level, repair leaks

and refill.

6. *
7. Check engine cooling airflow.
R ^

The Auto/Off/Manual switch

is set to OFF, but the engine
continues to run.

1. Defective switch

2. Defective control board

1. *

0

There is no AC output from

tlie generator.

1. Generator main line circuit

breaker open

2, Generator internal failure

1, Reset circuit breaker

to ON (or closed].

2. *

There is no transfer to

standby after utility
source failure.

1. Generator main line circuit

breaker open

2. Defective transfer svfitch coil
3. Defective transfer relay
4. Transfer relay circuit open
5. Defective control logic board

1. Reset circuit breaker

to ON (or closed).

2. *
3. *
4.
5. *

*Contact your nearest Generac/Guardian Authorized Dealer for assistance.