Section 1 — Generai Information

Guardian Liquid-cooied 8 kW Generators

GENERAL

INFORMATION

Figure 1.2 - Single- and Three-phase Delta

Generator AC Connection System

Figure 1.3 represents a single-phase, threenvlre
generator AC connection system. The stator assem­
bly in this system consists of a pair of stationaiy
windings with Pan leads brought out of each wincl-
ing. Each single nhnding can supply a 120-volt, 60-
Hertz AC output. When the two windings are con­
nected in series, a 240-volt, 60-Hertz AC output
results. Typically, the two "hot” leads in the circuit
are Wires 11 and 44. The neutral leads are the

junction of Wires 22 and 33.

Figure 1.3 - Single-phase

Generator AC Connection System

When utility source voltage has been restored, the

switch transfers back to the utility source voltage,
and the generator then shuts down,

1.5

MAIN CIRCUIT BREAKER

The generator’s main circuit breaker is included with

the unit as shipped from the factory. The breaker for
each unit is described as follows:

Mode! Number

Circuit Breaker Ratinq

04135-0

35A-2P-BQ2

04137-0

35A-3P-BQ3

1.6

ENGINE PROTECTIVE DEVICES

The engine has several safely switches tliat cause

it to automatically shut down under the following con­

ditions: low oil pressure, high coolant temperature,

low coolant level, and engine overspeed or overcrank.
See Figure 1.4 for the location of these devices.

4 1.6.1 LOW Oil PRESSURE SWITCH________________

This switch is normally closed {N.C.] but is held open
by engine oil pressure during engine running. Should

operating oU pressure drop below apprommately 15

psi, the switch contacts close, and die engine shuts

down automatically.

Figure 1.4 - Engine Protective Devices

Low Oil
Pressure Switch

1.4 , AUTOMATIC SYSTEM OPERATION

Wnen this generator, along with its transfer switch,

has been Installed and interconnected, a circuit
board in the generator panel continuously monitors
utility power source voltage. Should that voltage
drop below a preset value, and remain at such a low
state for a preset amount of time, the generator
cranks and starts. After the generator starts, the

transfer switch transfers load circuits so the genera­

tor can power them.

4 1.6.2 HIGH COOLANT TEMPERATURE SWITCH

This normally open (N.O.) thermostatic switch has

a sensing tip that is immersed in captive coolant.
Should the coolant temperature exceed approzd-

mately 124° C (256° F), the switch contacts close,

wTich causes the engine to shut clown automatically.

Generac® Power Systems, !nc.