Section 2 — Operation

Guardian Liquid-cooied 8 kW Generators

OPERATION

6

&

# 2.8.1 USING AN OPTIONAL GTS

_________ TRANSFER SWITCH_______________________

When you use a GTS-type transfer swatch, it con­

trols automatic operation and automatic transfer

as follows:

• Solid-state circuits in the transfer switch monitor

utility power source voltage.

• When utilitjr source voltage drops below a preset

level, transfer swdtch action closes the engine cir­
cuit. The engine then cranks and starts as con­

trolled by the generator's control module circuit
board.

* After the engine starts and when the generator

A.C output voltage and frequency have reached a
preset value, transfer switch circuits signal the
transfer switch main contacts to move to the

standby power source side. Generator AC output
then pownrs load circuits.

® When the utiliW power source voltage is restored

above a preset level and the return to utility
timer has timed out. the transfer switch solid-
state circuits signal the switch main contacts to
move back to their utility power source side.

» The engine cooldown timer stains and times out.

Then, the transfer switch circuit board action

opens the engine run circuit. The engine then
shuts down.

NOTE:

If

yonr

generator

is

installed

in

conjunction

with an optional GTS-type transfer switch, refer
to

the

applicable

transfer

switch

manual

for

exact

operating

parameters

and

timing

sequences.