Section 3 — Maintenance

Guardian Liquid-cooled 8 kW Generators

MAINTENANCE

3. When aJl of the oil has drained, install and tight­

en the oil drain hose cap.

4. Turn tile oil filter (Figure 3.1) countercloclcwise

and remove it. Dispose of the old filter.

5. Apply a light coating of engine oil to the seal of

new oil filter. Install tire filter and tighten by
hand only. DO NOT OVERTIGHTEN,

6. Remove the oil filler cap (Figure 3.1). Add the rec­

ommended oil (see Section 1.9, Page 7). DO NOT
FILL ABOVE THE DIPSTICK ■‘FULL” MARK.

-A

CAUTION A--------

After refilling the crankcase with oii, always
check the oil level on the dipstick. Never

operate the engine with the oil level below the
"Add" mark on the dipstick. Doing this could
damage the engine.

7. Start the engine and check for oil leaks.
8.

Check the oil level after checking for leaks to

ensure that the oil is filled to the proper level.

3.5

CHANGING THE ENGINE

AIR CLEANER

To replace the engine air cleaner, (Generac part

number 70941), simply remove the air cleaner
cover and replace the air filter making sure it is
positioned properly before reattaching the cover.

Figure 3.2 - Engine Air Cleaner

AIR CLEANER

(TPANSPAREMT ENCLOSURE FOR CLARITY)

See tile “Service Schedule," Section 3.13 (Page 16),
for recommended air cleaner maintenance.

3.6

BATTERY MAINTENANCE

The battery should be inspected per the “Service

Schedule,” Section 3.13 (Page 16). The following
procedure should be followed for inspection:

1. Inspect the battery posts and cables for tight­

ness and corrosion. Tighten and clean as
necessary.

2. Check the battery fluid level of unsealed batter­

ies and, if necessar/, fill wth DISTILLED

WATER ONLY. DO NOT USE TAP WATER IN

BATTERIES.

3. Have the s tate of charge and condition checked.

This should be done mth an automotive-type

battery hydrometer or load test.

-АЕВШЗ A-

A

A

Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after

charging. The slightest spark can ignite the gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or
other injury. Any area that houses a storage

battery must be properly ventilated. Do not
allow smoking, open flame, sparks or any spark
producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caustic

sulfuric add solution that can cause severe
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery, if you spill the fluid, flush

the affected area immediately with clear water.

Do not use any jumper cables or booster bat­

tery to crank and start the generator engine, if
the battery has completely discharged, remove

it from the generator for recharging.

A

-----

Ak

WARNING ---------

Be sure the utility power supply is turned off,
or sparking may occur at the battery posts as

you attach the cables and cause an explosion.

Be sure the Auto/Off/Manual switch is set to

the OFF position before connecting the battery

cables. If the switch is set to AUTO or MANUAL,

the generator can crank and start as soon as
the battery cables are connected.

Generac® Power Systems, inc. 13