Operation

Waveform Generation with Internal Hardware Timer

Six counters interact with the waveform, generating different
DAWR timings to produce various waveforms, as shown.

*timebase= 80 MHz

Table 4-3: Waveform Generation Timer Definition

Counter

Width Description

Note

UI_counter

32-bit

Update interval,
defining the update
interval between each
data output.

Update interval =
UI_counter / timebase*

UC_counter

32-bit

Update count, defining
the amount of data in a
waveform.

When value in
UC_counter is less
than the size of
waveform patterns, the
waveform is generated
incrementally.

IC_counter

32-bit

Iteration calculation,
defining how many
times the waveform is
generated.

DLY1_counter 32-bit

Defines the delay time
for waveform
generation after the
trigger signal.

Delay Time =
(DLY1_counter / Clock
timebase)

DLY2_counter 32-bit

Defines the delay time
to separate consecutive
waveform generation.
Effective only in
Iterative Waveform
Generation mode.

Delay Time =
(DLY2_counter / Clock
timebase)

Trig_counter

32-bit

Defines the acceptable
start trigger count when
re-trigger function is
enabled