6.1 Relay Contact Protection Circuits

The contacts are the most important elements of relay construc-
tions, Contact performance is conspicuously influenced by contact
material, voltage and current values applied to the contacts.

Another important issue is contact protection, a right contact pro-
tection circuit can suppress the counter EMF to a low level. How-
ever, note that incorrect use will result in an adverse effect. Typical
contact protection circuits are given below :

RC Circuit

This circuit is suitable for DC application. If the load is a timer,
leakage current flows through the RC circuit causing faulting oper-
ation.

The below circuit is suitable for both AC and DC applications. If
the load is a relay or solenoid, the release time lengthens. It’s
effective when connected to both contacts if the power supply volt-
age is 24V or 48V and the voltage cross the load is 100 to 200V.

Device Selection:

As a guide in selecting R and C,

Z

R : 0.5 to 1

Ω

per 1V contact voltage

Z

C : 0.5 to 1

μ

F per 1A contact current

Values vary depending on the properties of the capacity C acts to
suppress the discharge the moment the contacts open. Resistor R
acts to limit the current when the power is turned on the next time.

Contact

Inductive

Load

R C