Mounting and installation – Glow-worm Clearly Heat Pumps Envirosorb3 User Manual

Page 14

Advertising
background image

0020154078_00 - 02/13 - Glow-worm

14

MOUNTING AND INSTALLATION

4.4

Electrical

Installation

e

Danger!

Risk of electric shock due to an improper electri-

cal connection!

Improper electrical connection can cause electric

shock or might negatively affect the operational

safety of the product and might cause material

damage.

The electrical connection of the product must

be carried out only by a suitably qualified per-

son.

20 mm max.

2

1

Key

1 Electrical

wires

2 Insulation

When you connect the electrical wires to a connector on the

electronic board:

∙ Keep a distance of a maximum of 20 mm between

connector and the start of the insulation.

∙ Fix the electrical cables with the clamps installed inside

the heat pump.

4.4.1

Connecting the power input (mains

connection)

The external wiring must be earthed, with correct polarity and

in accordance with current standards.

∙ Always check that the Live and Neutral are connected

correctly.

The cables connecting the switchboard and the heat pump

must be:

- Suitable for a fi xed installation.

- weather resistant.

- equipped with wires adapted to appliance’s power rating.

∙ Connect the heat pump to an electrical panel via an

independent protection system (diff erential breaker with at

least 3 mm between each contact).

Additional protection may be required during installation to

ensure surge category II.

The power supply cut-off devices must allow complete

disconnection of the power under the conditions required for

over-voltage category III.

4.4.1.1 230V heat pump

b

Caution!

Risk of damage from too great voltage.

At mains voltages higher than 253 V, electronic

components may be destroyed.

Make sure that the rated voltage of the mains

is 230 V.

b

Caution!

Risk of malfunction due to the electrical supply.

If the imbalance between the phases of the elec-

trical supply is too large, a malfunction may occur.

Install the appliance on a electrical supply with

a maximum imbalance of 2% between phases.

X4

X9

EBUS

X7 FLOOR H

X2

21

1

2

Key

1 Heat pump power supply connection

2 Installation power supply and electric protection

Envirosorb3 8

Envirosorb3 11

Electricity supply

1/N/PE 230V 50Hz 1/N/PE 230V 50Hz

Circuit breaker

16 A - Type C or D

20 A - Type C or D

Recommended cable size

230V

3G x 2.5 mm²

3G x 2.5 mm²

∙ Connect a cable to the appliance’s power terminal.

∙ Pass the cables through the heat pump cable gland (see

section 4.4.3).

∙ Suitable breaker size and type must be used to fi t

installation site requirements.

∙ Cable size must be suitable for installation site

requirements

4.4.2

24V cable connection

X4

X9

EBUS

X7 FLOOR H

1

2

3

Key

1 eBUS connection to the heat pump (comply with the polarity ±)

2 Connect

the

fl oor heating protection device to the heat pump

3 e-BUS connection terminal on the control box