2 siting the unit, 1 site requirements, 2 installation minimum clearances – Glow-worm Clearly Heat Recovery User Manual

Page 10: 3 remote control, 4 atmosorb

Advertising
background image

10

2 Siting the Unit

2.1 Site Requirements

The site for the unit must be dry and frost-free. The system

installation must be planned in detail, with particular attention

to the positioning of the fresh air and exhaust air ducts and to

include sufficient sound insulation.

NOTE: The temperature of the unit can be considerably lower

than the temperature of the room, it is being installed in. To

avoid undesirable accumulation of condensate, the circulation

of fresh and exhaust air must be provided in the room.

The unit is wall-mounted and should preferably be close to a

drain outlet for the condensation drain.

• The unit must be installed with due consideration of the

requirement for adequate and practical air ducting and

services (fresh air and exhaust air, electrical power). Ensure

enough space is provided on top of the unit and at its sides to

be able to mount the required air ducts, additional silencers

and bypass unit, see diagram 2.1.

• The installation site must be selected so that the ductwork

distances to and from the unit are as short as possible.

• The wall to which the unit is to be mounted must be of a

sufficient load-carrying capacity for the weight.

• It is possible that the supplied fixing are not suitable for the

installation wall, then it is the responsibility of the installer to

provide the fixings.

• The condensate drain must be connected with the supplied

condensate drain trap and to the water outlet with an odour

trap (siphon).

• If the unit is mounted on an internal wall, do not select

a location directly above bedrooms due to possible sound

transfer. Always choose a location above a non-occupied

room such as a hall or bathroom.

• With wood-joist ceilings or similar you can provide additional

sound insulation by adding insulation between the joists.

• Always ensure that the condensate drain is free running.

• To avoid annoyance by excessive noise select a sound-

absorbing hose for final connections from the unit to the air

outlets.

• Install a silencer. This will help to neutralise possible noise

transmission between the unit and the air ducting and reduce

annoyance by noise.

• Keep the air supply inlet at a sufficient distance from

discharge air, exhaust air and drain ventilation. Comply with

the legal building rules and regulations.

• When installing the fresh air input and discharge air ducts

you will have to ensure sufficient separation to avoid that the

discharged air being re-circulated into the fresh air input.

To avoid re-circulation, the minimum recommended distance

between supply and extract is 2 metres.

2.2 Installation Minimum Clearances

• Please refer to diagram 2.1.

• For the installation, at least 100mm of free space on the

side of the device must be provided.

• For installation, filter replacement and maintenance works,

1 m working space in front of the ventilation unit is needed.

Over and beneath the device at least 30 cm are required.

2.3 Remote Control

• The remote control must be mounted such that there is

enough space around it to complete the electric wiring as well

as easy operation of the control.

• The remote control must be installed inside the living space

and be easily accessible. For further details see section

“Installation - Controls”.

2.4 Atmosorb

• Electrical connection above mains voltage socket with

230 V 50 Hz mains voltage.

The connection must comply with the current rules and

regulations.

Diagram 2.1

1000

100

300

100

300

0-1˚

600

14880

Advertising