7 Fault Finding

Indication

on the

display

Check/

component

Cause

Remedy

COM Err Fans turn with 20% PWM

Communication error between the PCB in the

unit and the remote control.

230 V eBUS line laid parallel in pipe or cable

channel.

Pull the mains plug and insert it again.

If this does not help to eliminate the error,

contact Glow-worm Customer Service.

LOCK

Both fans inoperative

Alarm input "X 14" opened.

Check whether a separate switch is

connected to "X 14". Check why the switch is

open.If this does not help to eliminate the

error, contact Glow-worm Customer Service.

SAI Err*

Temperature sensor outside air Temperature sensor defective (interrupted or

short-circuited).

Wiring interrupted.

Contact Glow-worm Customer Service.

EAI Err*

Temperature sensor exhaust

air

Temperature sensor defective (interrupted or

short-circuited).

Wiring interrupted.

Contact Glow-worm Customer Service.

EAO Err

Temperature sensor discharge

air

Temperature sensor defective (interrupted or

short-circuited).

Wiring interrupted.

Contact Glow-worm Customer Service.

SAO Err* Temperature sensor fresh air

Temperature sensor defective (interrupted or

short-circuited).

Wiring interrupted.

Contact Glow-worm Customer Service.

SFAN Err

Contact Glow-worm Customer Service.

EFAN Err

Contact Glow-worm Customer Service.

FILT

Check all filters for soiling.

Time for programmed filter timer expired.

Set the filter timer (in the installer level) to

RESET.

Error Messages in the Remote Control

Temperature in

o

C

Resistance in Ω

-20

95862

-10

54892

0

32510

10

19862

20

12486

25

10000

30

8060

40

5330

* Error message only with installed bypass

Resistance Values of the Temperature

Sensor