18

5 Commissioning

5.1 Function checks

Once all connections are correctly installed in accordance

with the wiring scheme, check the functions of the remote

control, the ventilation unit and the bypass. When doing so,

note that the unit must not be started until all ventilation ducts

are connected to the unit and the unit and all ductwork are

completely sealed.

In the user sections of the “Instructions for Use” manual you

will find in detail all the settings for the individual operating

modes and the special functions. For testing functions

proceed as follows:

• Select the “night” operating mode and check that the fans in

the domestic ventilation unit are operating at low output.

• Select the “day” operating mode and check that the fans in

the domestic ventilation unit are operating at medium output

(AIR2).

• Activate the special function”advance”. Check that the

fans in the domestic ventilation unit are operating at medium

output (AIR2).

• If the output stages are not correctly switched, you must

check the wiring on the terminals of the remote control and

the domestic ventilation unit.

5.2 Start-Up

The start-up and the operation of the unit as well as

instruction to the user must be done by a

competent person

approved at the time by the Health and Safety Executive.

Please note that the device can only be started up if all

ventilation pipes of the device are connected and the entire

device is closed.

As part of the start-up it is necessary to adjust the ventilation

unit.

The ventilation units are delivered with basic setting for both

fans. As each fresh air and exhaust air installation is different

and thus offers different external resistance in the air ducting

you will have to separately adjust the fresh air and the

exhaust air fan to suit.

You can adjust the domestic ventilation unit using the remote

control. Below are the necessary steps.

5.3 Adjustment of the Digital Remote

Control

To optimally match the system parameters to the required

conditions it is necessary to set these parameters with the

remote control, see diagram 5.1. The system parameters are

located in an upper operation level and should only be set by

a

competent person approved at the time by the Health and

Safety Executive.

5.4 Expert Technician Level

Hold down the “mode” button for about 10 seconds to go to

the installer level. The symbol appears on the display.

Then, by pressing the dial, it is possible to select the

functions. The functions shown in table 5.1 can be scrolled

through one after the other.

To change the parameters just press “prog”.

If you want to return to the basic display, shortly press the

“mode” button.

The adjustable air volume flows apply jointly to fresh air and

exhaust air.

Diagram 5.1