5 Commissioning

5.6 Testing of the bypass and other

functions

Go to the service/diagnostics level as described in

section 5.5. Now test successively all functions in accordance

with the above table. If the bypass is not connected or if a

sensor is defective, the display will show the “-” symbol.

5.7 Reset to the Factory Setting

• Press the “prog” button for 15 seconds to reset the controller

to the default setting.

As soon as the display lights up twice, the controller is

completely re-set to its default settings. This means that you

will have to perform all individual settings again.

5.8 Domestic Ventilation Unit Adjustment

Adjustment procedure

First of all ensure that the overall air flow calculated for the

installation is reached by the system. Then adjust the air

flow rates for the individual living spaces. Finally adjust the

individual air flow distribution within each living space.

Total Air Flow Adjustment

First adjust the desired air quantity calculated when the

system was designed with the remote control for all operating

modes (installer level). Proceed step by step as described in

table 5.1, page 19. In the table you will find the information for

the desired values.

NOTE: The planned air flow must be in the in the day mode

(2nd stage) because this is the standard operation mode.

Adjusting the air quantities at the system

1. Adjust all the exhaust and fresh air valves in the living

rooms to the middle opening of about 50 %. Then proceed in

accordance with the instructions given in the manufacturer

operating manual.

The air speed must not exceed 1.5 m/s at a distance of 50 cm

from the valve.

2. Make sure that all valves in the existing air duct manifolds

are completely opened.

3. Switch the domestic ventilation device into the operation

mode “day mode” using the remote control.

4. Measure the partial air flow at the strings with control

dampers if there are some available. Correct these settings if

required by adjusting the control dampers.

5. Open, if necessary, air inlet and air outlet valves if the

desired total air flow has not been reached.

6. Raise the ventilator revolution speed using the values in

table 5.1 if the total air flow is too low.

7. Go to the installer level in the remote control by pressing

the “mode” button for 10 seconds.

8. Press the

“prog” buttons until “C-AIR” appears on the

display.

9. Correct the inlet air flow by pressing the

- or + buttons until

the inlet and the outlet air volume are equal (see table 5.1).

5.9 Operator Delivery

Completely fill in the attached measurement report

(page 27) and hand it over to the operator.

Action

Display

Meaning

press mode

and prog

button for 3

seconds

BYP

ON

Bypass switches to summer mode

press +

button

ALAR

ON

Alarm output is activated

(contact closed).

press +

button

SAO/*

xx

o

C

Display of fresh air temperature (Supp-

ly Air Out)

press +

button

EAO/

xx

o

C

Display of the discharge air tempera-

ture at the frost protection sensor (Ex-

haust Air Out)

press +

button

EAI*

xx

o

C

Display of the exhaust air temperature

(Exhaust Air In)

press +

button

SAI/*

xx

o

C

Display of the outside air temperature

(Supply Air In)

press

prog button

AIR/

xx m

3

/h

Current air volume flow indication in

the ventilation unit. By turning the dial

it is possible to change the air quantity

during the test mode.

press

prog button

APPL/

1 / 2

Display of the unit type

1 = Atmosorb HRD 275

2 = Atmosorb HRD 350

Turn the dial to select the unit type.

press

prog button

Display

Display test: All symbols of the display

are indicated, however, not all symbols

of recoVAIR have a meaning.

press

prog button

VER1/

x.xx

Display of the software version of the

remote control

press

+ button

VER2/

x.xx

Display of the software version of the

recoVAIR PCB

press mode

and prog

button

Return to basic display

Functions of the service/diagnostics level

* These values can only be called with a bypass unit installed.
Please refer to diagram 5.1 for layout of control panel buttons: