Installation – Glow-worm Clearly Hybrid - Universal Module System User Manual

Page 22

Advertising
background image

0020096317_01 - 02/11 - Glow-worm

- 20 -

6.1.2 Heating

curve

The following menu allows you to select the heating curve (value

adjustable between 0.2 and 4 - factory setting: 0.5), which allows

you to obtain the maximum heating demand for the usual minimum

outdoor temperature for the region in which the sensor is installed.

The automatic heating curve function continually and automatically

seeks the most suitable value to ensure your comfort and

the effi ciency of your heating system. The optimum value is

obtained approximately 24 hours after the system is started. It is

recommended to activate this function.

1

Select Htg curve settings

on the screen.

2A

With Automatic htg curve

activated.

2B

With the Automatic htg

curve deactivated, you must

choose a heating curve.

2B.1

Select Htg curve setting

on the screen.

2B.2

Choose the heating

curve (see curve and

explanations after).

b

Ensure that the heating curve setting is compatible

with the installation.

Heating curve

A

B

1

2

3

Key

1 Older

properties

with radiators

2 Standard/modern

house

with radiators

3 Highly insulated modern house with low temperature radiators or

underfl oor heating

A Heating

fl ow temperature (°C)

B External

temperature

Case of a heat pump controlled by On/Off contact

Refer to the heat pump installation manual to access the

“after-sales” parameters listed below.

Set the heat pump heating curves complying with the

correspondences with the Systempro control unit heating

curves (see table below).

b

Incorrectly setting these parameters may signifi cantly

impact the system effi ciency.

- Setting of the heat pump parameter 112:

Heating curve of the Systempro

control unit

Heating curve

of the heat pump

0.1 ▸ 02

7

0.3 ▸ 0.4

8

0.5 ▸ 0.7

9

0.8 ▸ 0.9

10

1.0 ▸ 1.2

11

1.3 ▸ Max.

12

Example:

- Setting of the heat pump parameter 112:

Heating curve of the Systempro

control unit

Heating curve

of the heat pump

0.1 ▸ 0.2

7

0.3 ▸ 0.4

8

0.5 ▸ 0.7

9

0.8 ▸ 0.9

10

1.0 ▸ 1.2

11

1.3 ▸ Max.

12

In the case where the MODUZONE Z20 or Z30 option is installed:

if the curve setting is "1.2" on the control unit, the curve setting

will be "11" for heat pump parameter 112.