0020096317_01 - 02/11 - Glow-worm

- 30 -

12 Servicing

Consult each of the system component’s instructions for more

information about the corresponding maintenance operations.

13 Control unit maintenance menu

Enter the installer maintenance access code (35) into the

control unit.

13.1 Test

menu

This menu allows you to test the operation of all appliances and

the system (boiler, HP, zone valves,) present in the installation.

Boiler test

i

Le test de la chaudière est possible seulement si elle

est raccordée en eBus (schéma 10 and 5).

1

Select System tests on the

screen.

2

Select Boiler on the screen.

Heat pump test

1

Select System tests on the

screen.

2

Select Heat pump on the

screen.

This menu allows you to:

- issue a heating demand to the heat pump (*),

- activate the pump (**)

- activate the fan (**)

- activate the 4-way valve (**)

- activate the crankcase heater (**)

- activate the electrical resistance heater (**)

- activate the heat exchanger’s resistance heater (**)

- activate the defrosting (**)

(*) In the case of a heat pump controlled by an On/Off contact,

perform an On/Off on the heat pump for a few seconds on the

heat pump before starting the heating demand.

(**) Only available with an eBus heat pump.

System test

1

Select System tests on the

screen.

2

Select System on the

screen.

3

Activate the hydraulic

module pump.

Heating zones test

i

The heating zones can only be tested if you have

installed multiple zone valves.

1

Select System tests on the

screen.

2

Select Zones on the

screen.

3

Activate the multi-zone kit

valve for each zone.

MAINTENANCE

EN