Maintenance – Glow-worm Clearly Hybrid - Universal Module System User Manual

Page 31

Advertising
background image

0020096317_01 - 02/11 - Glow-worm

- 29 -

Fault

codes Description

Cause

Solution

030

Failure in communication with the zone

1 wireless room thermostat.

The room thermostat is too far from

the control unit.

There is a problem with the batteries

in room thermostat.

Check the RF signal quality via the Climapro2 RF installer

menu.

Check the location of the thermostat.

Check that the thermostat’s batteries are installed in their

compartment.

Make sure the battery polarity is not reversed.

Make sure the batteries are not dead.

If so, replace them with new batteries

031

Failure in communication with the zone

2 wireless room thermostat.

032

Failure in communication with the zone

3 wireless room thermostat.

033

Failure in communication with the zone

4 wireless room thermostat.

034

Failure in communication with the zone

5 wireless room thermostat.

035

Failure in communication with the zone

6 wireless room thermostat.

036

Failure in communication with the

wireless outdoor sensor

The wireless outdoor sensor is too far

from the control unit.

Check the location of the outdoor sensor. Check that the

sensor’s power supply is correctly provided by a photovoltaic

cell.