Introduction – Glow-worm Clearly Hybrid - Universal Module System User Manual

Page 7

Advertising
background image

0020096317_01 - 02/11 - Glow-worm

- 5 -

Key

1 Overheating safety (UFH shown, but can be underfl oor or radiators)

2 Hydraulic

module

3 Heating

circuit

4 Climapro2 RF programmable wireless room thermostat

5 Systempro control unit

6 Wireless outdoor sensor

7 EBus

boiler

8 Heat pump electrical supply + protection (This must have it's own

single isolation)

9 Non-return valve (recommended to prevent burner ignition triggered

by thermo-siphoning)

10 EBus heat pump

11 Heat pump circuit fi lter (not supplied)

12 Glycol PRV discharge

A Heating circuit return

B Heating

circuit

fl ow

C Boiler circuit return

D Boiler

circuit

fl ow

E

Heat pump circuit fl ow

F

Heat pump circuit return

G Heat pump circuit safety valve discharge

Application conditions

- The Systempro control unit manages the operation of the

boiler, the heat pump and the module.

- The Systempro control unit manages up to 3 heating zones.

- Each wireless room thermostat can control a heating zone.

- The installation can be performed with a low-temperature

underfl oor heating (heating outlet temperature < 50°C) or low

temperature radiators (heating outlet temperature < 70°C).

e

Use 0.75 mm² section cables for the electrical

connections to the control unit.

Control unit settings

Description of main settings

Setting

Diagram no.

10

Did you install a multizone kit ?

No

Heating curves

0.1 - 1.5

Max. heating fl ow temperature

30°C < T < 70°C

Energy effi ciency ratio

To be defi ned

INTRODUCTION

EN

Advertising