Assembly and installation 5

0020154078_03 Envirosorb₃ Installation instructions

17

7.

Make sure that the condensate drain pipe ends in a
gravel bed.

Note
The condensate drain pipe must not be
longer than 365 mm, otherwise it may freeze
over.

8.

Route the condensate drain pipework with a downward
gradient.

5.4

Carrying out the electrical installation

30 mm max.

1

2

1 Connecting wires

2 Insulation

Danger!
Risk of death from electric shock as a res-

ult of an improper electrical connection!
An improper electrical connection may neg-

atively affect the operational safety of the

product and result in material damage or per-

sonal injury.

The electrical installation must be carried

out by a suitably qualified competent per-

son who is responsible for complying with

the existing standards and directives.

1.

Only strip a maximum of 3 cm from the outer sheathing
of the flexible lines.

2.

Secure the conductors in the connection terminals.

5.4.1

Establishing the power supply

The external mains connection cable must be earthed and
connected with the correct polarity and in accordance with
the valid regulations.

Check that the mains connection cable is connected cor-
rectly.

The cables that connect the product to the fuse box must:

– Be suitable for fixed installation,
– Be weatherproof,
– Be equipped with a wire cross-section that is necessary

for the product performance.

Connect the product using a fixed connection and a parti-
tion with a contact opening of at least 3 mm (e.g. fuses or
power switches).

In order to meet the overvoltage category II requirements,
further fuse protection may be required.

To meet the overvoltage category III conditions, the parti-
tions must ensure a complete separation of the power sup-
ply.

5.4.2

Standard tariff

5.4.2.1 230 V connection

X4

X9

EBUS

X7

FLOOR H

X2

21

2

1

1 Mains connection terminal

in the product

2 Partition

Caution.
Risk of material damage due to high con-

nected voltage.
At mains voltages greater than 253 V, elec-

tronic components may be damaged.

Ensure that the rated voltage of the mains

is 230 V.

Connect the mains connection cable to the product's
power supply connection.

En-
virosorb

3

5

En-
virosorb

3

8

En-
virosorb

3

11

En-
virosorb

3

15

Power supply

1/N/PE
230 V
50 Hz

1/N/PE
230 V
50 Hz

1/N/PE
230 V
50 Hz

1/N/PE
230 V
50 Hz

Fuse

16 A -
type C
or D

16 A -
type C
or D

20 A -
type C
or D

20 A -
type C
or D

Recommended
cable dimension

3G x
2.5 mm²

3G x
2.5 mm²

3G x
2.5 mm²

3G x
2.5 mm²

To ensure that people are safe, install a separate 30 mA
residual-current-operated circuit-breaker for the heat
pump.

Guide the mains connection cable through the product's
cable duct (PEG screwed connection).