Notes on the documentation 2

0020154078_03 Envirosorb₃ Installation instructions

7

2

Notes on the documentation

2.1

Observing other applicable documents

You must observe all the operating and installation in-
structions included with the system components.

2.2

Storing documents

Pass these instructions and all other applicable docu-
ments on to the system operator.

2.3

Applicability of the instructions

These instructions apply to units with the following type des-
ignations and article numbers only:

Type designation

Art. no.

Envirosorb

3

5

0010014421

Envirosorb

3

8

0010011967

Envirosorb

3

11

0010011968

Envirosorb

3

15

0010014422

The seventh to sixteenth digits of the serial number on the
identification plate form the article number.

3

System overview

3.1

Safety devices

– The product can work at the following outside temperat-

ures:

Envirosorb

3

5

Envirosorb

3

8,
Envirosorb

3

11,
Envirosorb

3

15

Heating mode

−15 … 28 ℃

−20 … 28 ℃

Cylinder charging mode

−15 … 46 ℃

−20 … 46 ℃

– If the product's coolant circuit pressure exceeds the max-

imum pressure of 4.15 MPa (41.5 bar), the high-pres-
sure pressure switch switches the product off. Follow-
ing a waiting period, the product attempts to start once
more. After three failed start attempts in succession, a
fault message is displayed.

– If the product is switched off, the crankcase housing

heating is switched on when the compressor outlet tem-
perature reaches 7 °C in order to prevent possible dam-
age caused by switching it back on.

– If the compressor inlet temperature and the compressor

outlet temperature are below 1 °C, the compressor does
not start up.

– A temperature sensor on the compressor outlet limits the

product's operation if the measured temperature exceeds
the maximum permissible temperature. The maximum
permissible temperature depends on the evaporation and
condensation temperature.

– The product measures the flow rate of the connected

heating circuit when starting up the product.

– If the heating circuit temperature falls below 3 °C, the

product's frost protection function is automatically ac-
tivated as the heating pump is started. In addition, frost

protection agent should be added to the heating water as
the heating water temperature may fall below the freez-
ing point in the event of a power cut, which poses a risk
of frost to the heating installation.

Note
Operating the heat pump outside the application
limits results in the heat pump being switched off
by the internal control and safety devices.

3.2

Functionality

The product comprises the following circuits:

– The coolant circuit releases heat into the heating circuit

by means of evaporation, compression, condensation
and expansion

– The heating circuit

3.2.1

Heating mode

1

2

3

4

5

6

1 Evaporator

2 4-way valve

3 Fan

4 Compressor

5 Electronic expansion valve

6 Plate heat exchanger

3.2.2

Thawing

1

2

3

4

5

6

1 Evaporator

2 4-way valve

3 Fan

4 Compressor

5 Electronic expansion valve

6 Plate heat exchanger

3.2.3

Application limits

Operation of the pump outside the application limits results in
the heat pump being switched off by the internal control and
safety devices.