Bypass

The boiler is fitted with an automatic bypass which can be

adjusted to suit your system requirements.

• Ensure that under no circumstances does the flow rate drop

below the figure specified, refer to chapter "Technical data".

Filling the sealed system

i

The water pressure at the boiler must be at least

1.2bar to operate the filling loop. If the pressure

is less than 1.2bar an external filling loop must be

fitted. If this pressure is not available contact the

local water authority.

Suitable external filling systems are shown diagrammatically,

see diagram below.

3

2

1

3

2

1

4

8

9

7

5

7

6

5

Key

1 Heating flow circuit

2 Heating return circuit

3 boiler

4 Double check valve assembly

5 Domestic cold water supply in

6 Temporary filling loop (remove immediately after filling)

7 Drain point

8 Back flow prevention device

9 Tundish

The system should be pressurised to 0.8bar, indicated on the

digital display with no heating demand.

Drain points

Drain taps must be provided at all low points of the system,

which will allow the entire system to be drained.

Drain taps shall be to the current issue of BS2879.

Water treatment

Existing system- It is essential that prior to installing the new

boiler the system is thoroughly flushed.

New system- For optimum performance after installation, the

boiler and its associated central heating system should also be

flushed.

Flushing shall be carried out in accordance with BS 7593, a

chemical cleanser can be used either Sentinel X300, X400 or

Fernox F3 are suitable.

It is recommended to flush existing systems first before fitting

the new boiler.

• Ensure all cleanser is removed from the whole system before

adding an inhibitor.

For long-term corrosion protection after flushing, an inhibitor

suitable for stainless steel heat exchangers can be used. Either

Sentinel X100 or Fernox F1 inhibitor can be used.

The boiler is suitable for use on systems using softened water.