Installation – Glow-worm Ultracom2 sxi User Manual
Page 21

0020092785_02 - 05/10 - Glow-worm
- 19 -
9.2.3
Multiple boiler chimney flue
Ø 60/100 mm (C43 type installation)
b
The flue connecting from the appliance to
the flue system must be supplied from the
manufacturer of the boiler.
b
C43 flue systems must not be a 'pressurised
system' but act under natural draught principles
b
C43 type flue systems must have their
own condensate drain fitted and not allow
condensate to mix into other appliances
L
B
A
1
2
3
4
5
Key
1 Pressure balancing system
2 Air-inlet pipe
3 Collector pipe
4 boiler
5 Inspection hatch
A final storey
B Ground floor
Type
Max length (L)
Ø 60/100
10 m
Each time an additional 90° bend is necessary (or 2 at 45°), the
length (L) must be reduced by 1 m.
Model
12sxi
18sxi
30sxi
Exhaust mass rate (g/s)
At min thermal load (40°C/30°C)
1.9
2.4
4.1
At max thermal load (80°C/60°C)
5.5
8.3
13.8
Exhaust temperature (°C)
At min thermal load (40°C/30°C)
47
45
41
At max thermal load (80°C/60°C)
69
65.7
71.4
INSTALLATION