Installation – Glow-worm Ultracom2 sxi User Manual

Page 21

Advertising
background image

0020092785_02 - 05/10 - Glow-worm

- 19 -

9.2.3

Multiple boiler chimney flue

Ø 60/100 mm (C43 type installation)

b

The flue connecting from the appliance to

the flue system must be supplied from the

manufacturer of the boiler.

b

C43 flue systems must not be a 'pressurised

system' but act under natural draught principles

b

C43 type flue systems must have their

own condensate drain fitted and not allow

condensate to mix into other appliances

L

B

A

1

2

3

4

5

Key

1 Pressure balancing system

2 Air-inlet pipe

3 Collector pipe

4 boiler

5 Inspection hatch

A final storey

B Ground floor

Type

Max length (L)

Ø 60/100

10 m

Each time an additional 90° bend is necessary (or 2 at 45°), the

length (L) must be reduced by 1 m.

Model

12sxi

18sxi

30sxi

Exhaust mass rate (g/s)
At min thermal load (40°C/30°C)

1.9

2.4

4.1

At max thermal load (80°C/60°C)

5.5

8.3

13.8

Exhaust temperature (°C)
At min thermal load (40°C/30°C)

47

45

41

At max thermal load (80°C/60°C)

69

65.7

71.4

INSTALLATION

Advertising