Hydronic section – WaterFurnace Envision Hydronic (NSW) User Manual

Page 10

Advertising
background image

10

NSW INSTALLATION MANUAL

Hydronic Section

General guidelines are shown below for component

selection and design/installation criteria for the piping

system. Local codes supersede any recommendations in

this manual.

Shut Off/Flow Regulation Valves

Use full port ball valves or gate valves for component

isolation. If valves are going to be used frequently, ball

valves are recommended. Globe valves are designed for flow

regulation. Always install globe valves in the correct direction

(fluid should enter through the lower body chamber).

Check valves

Swing check valves must be installed in the horizontal

position with the bonnet of the valve upright. Spring check

valves can be mounted in any position. A flow check valve

is required to prevent thermo-siphoning (or gravity flow)

when the circulator pump is off or when there are two

circulators on the same system.

Storage (Buffer) Tank

A buffer tank is required for all hydronic heating systems

using Envision NSW heat pumps. The tank should be sized

to provide 2 gallons of storage capacity for every one

thousand Btuh’s of nominal heat pump capacity.

Pressure Relief Valve

Most codes require the use of a pressure relief valve if a

closed loop heat source can be isolated by valves. Even

if local code does not require this device, WaterFurnace

recommends its installation. If the pressure relief valve in

the buffer tank is not already rated at 30 psi (207 kPa)

maximum pressure, one must be installed. The pressure

relief valve should be tested at start up for operation. Note

that the waste pipe must be at least the same diameter

as the valve outlet (never reduce), and valves may not be

added to this pipe. The bottom of the pipe must terminate

at least 6” (15 cm) above the floor. If the piping is connected

to a drain, there must be an air gap.

Backflow Prevention Check Valves

Most codes require backflow prevention check valves.

Note that a single check valve is not equal to a backflow

prevention check valve. Even if local code does not require

this device, WaterFurnace recommends its installation. This

is particularly important if the system will use antifreeze.

Pressure Reducing Valves or Feed Water Valves

This valve lowers the pressure from the make-up water line

to the system. Most are adjustable and directional. A “fast

fill” valve is required for initial filling of the system. Some

have screens, which must be cleaned after the initial filling.

If there is a restriction in the screen, the system could go to

0 psi (0 kPa), potentially causing pumps(s) failure. A valve

should be installed on each side of the pressure reducing

valve for servicing. Both valves should have tags reading

“Do not shut this valve under normal operation – service

valve only.”

Expansion Tanks

Expansion tanks are required on hydronic systems to help

absorb the pressure swings as the temperature in the

system fluctuates.

Elbows/Tees

Long radius elbows or two 45° elbows will lower pressure

drop. Standard tees have a greater restriction on the “T”

portion than tees designed with angled outlet ports.

Antifreeze

Antifreeze is required if any of the piping system is located

in areas subject to freezing.

Dielectric Unions

Dielectric unions are recommended whenever connecting

two dissimilar metals to one and other to prevent electro-

galvanic corrosion.

When using the various types of hydronic heat distribution

systems, the temperature limits of the geothermal system

must be a major consideration. In new construction, the

distribution system can easily be designed with the

temperature limits in mind. In retrofits, care must be

taken to address the operating temperature limits of the

existing distribution system. The maximum storage tank

temperature for the Envision NSW is 130°F (54.4°C). Typical

in floor radiant systems require much lower temperatures,

typically 100°-115°F, which is ideal for the Envision NSW.

Advertising