Standard control diagnostic table, Troubleshooting cont, Troubleshooting controls – WaterFurnace Envision Hydronic (NSW) User Manual

Page 47

Advertising
background image

47

NSW INSTALLATION MANUAL

Troubleshooting cont.

DISPLAY

FAILURE

DIAGNOSTIC

DC

Freeze detection thermistor is closed (shorted)

Replace the freeze detection thermistor

(clip-on thermistor)

DO

Freeze detection thermistor is open

Verify that the freeze detection thermistor is

secured properly in the board connector. If the

connection is secure, replace the thermistor.

FP

Freeze detection

The water going through the unit has reached the

freeze point setting (P=5, CL=15, OL=30).

Verify that the freeze detection setting is correct

for the application.

HC

Water set point thermistor is closed (shorted)

Replace the water set point thermistor

(threaded thermistor).

HP

High Pressure

The unit has cut out on high pressure. Discharge

pressure is >600.

LP

Low Pressure

The unit has cut out on low pressure. Suction

pressure is <40

PO

Water set point thermistor is open

Verify that the water set point thermistor is

properly secured in the board connector. If the

connection is secure, replace the thermistor.

Troubleshooting Controls

Check the unit. If a lockout mode is displayed, refer to the

table below to determine the meaning of the failure. Follow

the procedure listed to correct the problem.

Check the mode:

1. If the unit is running on the internal aquastat, verify the

unit is in “Primary” mode. The SL should be set to 0 in

the setup menu.

2. If the unit is running on an external aquastat, the SL

should be set to 1.

Check the jumpers on the control board:

1. Refer to the Control Board with Jumper illustration in

the Converting to a Dedicated Cooling Unit section to

see the location of the jumper on the board. If the unit is

a heating only unit, the jumper should be across 1 and 2.

2. If the unit is a cooling only unit, the jumper should be

across 2 and 3.

3. If the unit is a reversible unit, the jumper should be

across 3 and 4.

Check the thermistor calibration:

1. Using a thermometer in the P/T port, check the

incoming water temperature.

2. Verify that the measured temperature is within 3

degrees of the temperature displayed on the unit.

3. If it is not, adjust the calibration in the setup menu.

Standard Control Diagnostic Table