NSW INSTALLATION MANUAL

Staging with Primary/Secondary Mode

Staging is only possible with dedicated heating or cooling

units. Reversible units cannot be staged. Staging can be

accomplished with primary/secondary modes or by using

an aquastat.

The first stage must be setup as a primary unit. All other

units must be setup as secondary units. The set point is

stored in the primary unit. Once the set point in the primary

unit has been satisfied, all units will immediately shutdown.

WARNING: Do not stage more than 6 units.

C

G

W1

L

X1

Y2

O

Y1

W2

S

X2

R

C

G

W1

L

X1

Y2

O

Y1

W2

S

X2

R

C

G

W1

L

X1

Y2

O

Y1

W2

S

X2

R

Wiring for Primary/Secondary Unit Staging

First Stage

Second Stage

Third Stage

NOTES: X1 = Secondary output

Y1 = Compressor call

Staging with Aquastat

When staging units using an Aquastat, all units must be

setup as secondary units.

WARNING: Do not stage more than 6 units.

(

)

C

G

W1

L

X1

Y2

O

Y1

W2

S

X2

R

C

G

W1

L

X1

Y2

O

Y1

W2

S

X2

R

Typical Aquastat

Wiring for Dedicated Heating or Cooling Units

with Aquastat

First Stage

Second Stage

NOTES: X1 = Secondary output

Y1 = Compressor call

R = 24 VAC