Converting to a dedicated cooling unit – WaterFurnace Envision Hydronic (NSW) User Manual

Page 26

Advertising
background image

26

NSW INSTALLATION MANUAL

Converting to a Dedicated Cooling Unit

Procedure to Convert a Heating Only Unit to a

Cooling Only Unit

All non-reversible NSW units are built at the factory as

dedicated heating units. Follow the procedures below to

make the unit a dedicated cooling unit.

1. Shut off all power to the unit.

2. Remove the top and access panel.

3. Remove the brass in-well thermistor from the load

water-in line.

4. Remove the brass plug from the source water-in line.

5. Place new Teflon

®

tape on the threads of the brass in-

well thermistor.

6. Thread the brass in-well thermistor into the source

water-in line.

7. Make sure the thermistor wires do not touch the

discharge line.

8. Place new Teflon

®

tape on the threads of the brass plug.

9. Thread the brass plug into the load water-in line.

10. Refer to the labels on the unit for the location of ports

and lines.

11. Connect the “Source Water-In” line to the port marked

“Load Water-In.” Then, connect the “Source Water-Out”

line to the port marked “Load Water-Out.”

12. Connect the “Load Water-In” line to the port marked

“Source Water-In.” Then, connect the “Load Water-Out”

line to the port marked “Source Water-Out.”

Control Board with Jumper

P4

P5 Key Pad

(Interface)

P9

Not Used

P2

P1

13. Open the control box.

14. Find the connection marked “P4” as shown in the

Control Board with Jumper illustration.

15. Move the “P4jumper from across 1 and 2 to across 2

and 3.

16. Close the control box and secure the screws.

17. Replace the top and access panel.

18. Make sure all screws have been re-installed.

19. Turn on the power.

20. Using the touch-pad, press the UP arrow.

21. The displays should blink “44” to show set point. Now,

the unit should operate as a cooling only unit.

Jumper Pin Location

The location of the jumper pin determines the controller’s

mode of operation. Move the jumper pins to the correct

location for dedicated heating, dedicated cooling or

reversible settings as indicated below.

Dedicated heating

- 1 & 2 *

Dedicated cooling

- 2 & 3

Reversible

- 3 & 4 *

* Indicates factory setting.

NOTE: A reversible unit can not be configured to heating only.