NSW INSTALLATION MANUAL

Operating Limits

Heating with High Source Temperatures

Heating water with a water to water unit using high source

temperatures can lead to operating conditions that fall

outside of the system operating range. The condition occurs

when the loop (source) temperature exceeds 70°F [21.1°C]

with a full flow of 3 GPM per ton [0.054 LPS per kW].

Under this scenario, the evaporating temperature can fall

outside of the compressor operating window.

To allow the system to operate correctly, restricting the

source side flow when the evaporating temperature

exceeds 55°F [12.7°C] is recommended. One way of

accomplishing this is to use a flow-restricting valve on the

source loop circuit that is controlled by the evaporating

temperature. Locate the sensing device on the refrigerant

inlet of the evaporator.

As an alternative to the evaporating temperature, the

suction line temperature can be monitored with the same

control capability. In this control, temperature should be a

maximum of 65°F [18.3°C].

Operating Limits

Cooling

Heating

°F

°C

°F

°C

Source Side Water Limits

Minimum Entering Water

30

-1.1

20

-6.7

Normal Entering Water

85

29.4

60

15.6

Maximum Entering Water

110

43.3

90

32.2

Load Side Water Limits

Minimum Entering Water

50

10.0

60

15.6

Normal Entering Water

60

15.6

100

37.8

Maximum Entering Water

90

32.2

120

48.9

NOTES: Minimum/maximum limits are only for start-up

conditions, and are meant for bringing the space up to

occupancy temperature. Units are not designed to operate

at the minimum/maximum conditions on a regular basis.

The operating limits are dependant upon three primary

factors: 1) entering source temperature, 2) entering load

temperature, and 3) flow rate (gpm). When any of the

factors are at the minimum or maximum levels, the other

two factors must be at the normal level for proper and

reliable unit operation. Consult the Capacity Tables for each

model to determine allowable normal operating conditions.

Units are not designed for outdoor installation.

Pressure Drop

Model

GPM

Pressure Drop (psi)

60°F

80°F

100°F

120°F

018H

3.0

0.5

0.4

0.4

0.3

4.0

1.4

1.3

1.2

1.2

5.0

2.2

2.1

2.1

2.0

6.0

3.0

2.9

2.9

2.8

025H

4.0

1.3

1.3

1.2

1.2

5.5

3.0

2.9

2.8

2.7

7.0

4.6

4.4

4.3

4.1

8.5

6.7

6.5

6.4

6.2

7/13/09

NOTES: Temperatures are Entering Water Temperatures.

Double wall vented coax for heating potable water

NSW Vented Only Load Side

Model

GPM

Pressure Drop (psi)

30°F

60°F

80°F

100°F

120°F

018R*

3.0

0.5

0.4

0.4

0.3

0.3

4.0

1.1

0.9

0.9

0.8

0.8

5.0

1.6

1.4

1.4

1.3

1.3

6.0

2.1

1.9

1.9

1.8

1.8

025R*

4.0

0.7

0.6

0.4

0.3

0.3

5.5

1.3

1.1

0.9

0.7

0.6

7.0

1.9

1.7

1.5

1.3

1.2

8.5

2.6

2.4

2.2

2.0

1.9

040H/R

5.0

0.9

0.6

0.6

0.5

0.5

7.5

2.3

2.1

2.0

1.9

1.8

10.0

3.7

3.5

3.3

3.2

3.0

12.5

5.0

4.7

4.4

4.2

4.0

050H/R

8.0

1.7

1.4

1.4

1.3

1.3

11.5

3.6

3.4

3.2

3.0

2.8

15.0

5.6

5.4

5.0

4.6

4.2

18.5

8.3

8.1

7.6

7.2

6.8

060H/R

9.0

1.4

1.1

1.0

1.0

0.9

13.5

4.2

3.9

3.5

3.1

2.7

18.0

6.9

6.7

6.0

5.2

4.5

22.5

10.7

10.5

10.0

9.4

8.7

075H/R

10.0

3.2

3.0

2.8

2.7

2.5

14.5

5.5

5.3

5.1

4.9

4.7

19.0

7.9

7.6

7.3

7.1

6.8

23.5

11.5

11.3

11.0

10.8

10.5

8/9/10

NOTES: Temperatures are Entering Water Temperatures

*Domestic water heating units source side
pressure drop and reversible units load and
source pressure drop.