AHRI/ISO 13256-2 Performance Ratings

English (IP) Units

NOTE: All ratings based upon 208V operation.

Model

Capacity

Modulation

Flow Rate

Water Loop Heat Pump

Ground Water Heat Pump

Cooling

86°F Source
53.6°F Load

Heating

68°F Source

104°F Load

Cooling

59°F Source
53.6°F Load

Heating

50°F Source

104°F Load

Load

Gpm

Source

Gpm

Capacity

Btuh

EER

Btuh/W

Capacity

Btuh

COP

Capacity

Btuh

EER

Btuh/W

Capacity

Btuh

COP

Energy

Star

Compliant

018

Single

5

5

16,400

14.0

22,200

4.5

18,800

22.9

18,500

3.7

Yes

025

Single

7

7

23,700

13.6

32,800

4.6

26,700

21.2

27,100

3.8

Yes

040

Single

10

10

35,900

15.5

47,900

4.8

40,900

23.4

39,100

3.9

Yes

050

Single

15

15

49,800

13.9

65,000

4.4

55,600

21.6

54,200

3.7

Yes

060

Single

18

18

55,400

13.6

78,000

4.7

62,500

20.6

63,200

3.8

Yes

075

Single

19

19

66,000

12.3

93,100

4.2

74,100

18.0

77,100

3.5

No

Model

Capacity

Modulation

Flow Rate

Ground Loop Heat Pump

Cooling

77°F Source
53.6°F Load

Heating

32°F Source

104°F Load

Load

Gpm

Source

Gpm

Capacity

Btuh

EER Btuh/W

Capacity

Btuh

COP

Energy

Star

Compliant

018

Single

5

5

17,300

16.6

14,700

3.1

Yes

025

Single

7

7

24,700

16.1

22,000

3.1

Yes

040

Single

10

10

37,700

17.5

30,500

3.1

Yes

050

Single

15

15

51,500

16.4

44,200

3.1

Yes

060

Single

18

18

58,000

16.1

50,100

3.1

Yes

075

Single

19

19

68,400

14.0

61,500

2.9

No