Optional controls – WaterFurnace Envision Hydronic (NSW) User Manual

Page 32

Advertising
background image

32

NSW INSTALLATION MANUAL

FX10 Control

The FX10 control provides unparalleled capability

in several areas including performance monitoring,

energy management, and service diagnosis, and then

communicates it all thru standard DDC protocols like N2,

Lon and BACnet (MS/TP @ 19,200 Baud Rate).

The most unique feature is integrating the FX10 into the

Envision Series as both the heat pump and DDC controller

providing both a cost advantage and providing features

not typically found on WLHP controls. This integration

allows heat pump monitoring sensors, status and service

diagnosis faults to be communicated thru the DDC direct

to the building automation system (BAS), giving building

supervisors detailed and accurate information on every

piece of equipment without removing an access panel!

Control

General Description

Application

Display/Interface

Protocol

The FX10 microprocessor control is self
contained control featuring LP, LOC, HP, LWT,
and condensate overflow fault modes can be
displayed on BAS system. Optional handheld
Medium User Interface (MUI) Control can be
used for additional setup or servicing.
Program customization is possible.

Cannot be integrated with
centralized building automation
systems. Software can be
customized for specific
projects.

Optional Medium
User Interface (MUI)
can be used as a
field service tool.

Standalone

FX10 Control functions as both unitary heat
pump control and DDC communication,
therefore detail operational and fault
information is available to BAS. Other
features are same as FX10 with addition of
Johnson Controls N2 compatibility.

Same as FX10 with Johnson
Controls N2 BAS compatibility.

Optional Medium
User Interface (MUI)
can be used as a
field service tool.

Johnson
Controls
N2 network

FX10 Control functions as both unitary heat
pump control and DDC communication,
therefore detail operational and fault
information is available to BAS. Other
features are same as FX10 with addition of
LonWorks compatibility.

Same as FX10 with LonWorks
BAS compatibility.

Optional Medium
User Interface (MUI)
can be used as a
field service tool.

LonWorks

FX10 Control functions as both unitary heat
pump control and DDC communication,
therefore detail operational and fault
information is available to BAS. Other
features are same as FX10 with addition of
BACnet compatibility.

Same as FX10 with BACnet
BAS compatibility.

Due to communication speed,
no more than 30 units should
be connected to a single trunk
of the network.

Optional Medium
User Interface (MUI)
can be mounted or
used as field service
tool.

BACnet -

MS/TP

(19,200 Baud Rate)

FX10

FX10 w/N2

FX10 w/LonWorks

FX10 w/BACnet

Optional Controls

Advertising